Logo Microflex101-0014
In LinK – HM
Modemový modul s protokolem HART
with HART Device to Modbus Accumulator
for OEM Applications
Instalační software
Návod k instalaci a obsluze

Modemový modul InLink-HM 101-0014 s protokolem HART

Microflex InLink HM 101 0014 HART Protocol Modem Module

InLink-HM 101-0014 is a complete OEM HART® protocol modem module with managed HART host timing to function as either a primary or secondary HART host – eliminating the need for external CD monitoring and RTS control. It can also be used as a HART to Modbus accumulator polling up to 16 HART devices. For evaluation and development support, the InLink-HM module is compatible with the 101-0003 InLink evaluation board and pin-compatible with the InLink-TC module. The InLink-HM module is also compatible with the InLink-HM Evaluation Board RS-485 (part number 101-0093). Compatibility of the InLink-HM module with the InLink-HM evaluation board RS-485 requires Firmware version 6 or higher.

InLink-HM can be easily interfaced to most micro-controllers using only two I/O pins: transmit data (TXD) and receive data (RXD), typically connected to USART I/O. Unlike many HART modems, communications direction control is managed internally, so there is no need to handle tricky request-to-send (RTS) and carrier-detect (CD) handshake timing, greatly simplifying software development.

As a HART protocol modem, InLink-HM receives packets on the TXD input pin, at the configured baud rate and parity setting, and then sends the packet to the HART loop. After sending the packet, InLink-HM switches the modem to receive to acquire the reply. The reply is transmitted on the RXD output pin at the configured baud rate and parity setting. The DE output pin provides RS-485 half-duplex transceiver data direction control.

InLink-HM can be configured to continuously poll up to 16 HART devices and save the HART device data into Modbus registers. Modbus RTU commands can then be used to read the HART device data. Configuration is simple using the included HM Configuration software. Settings are saved in Modbus RTU registers, so Modbus RTU commands can also be used to edit the InLink settings. The InLink-HM module can be restored to default settings using the HM Configuration software.

620-0020 R4 Microflex 2016-2025

InLink-HM Block Diagram

Microflex InLink HM 101 0014 HART Protocol Modem Module - InLink-HM Block Diagram

Popis operace

InLink-HM includes a complete HART protocol modem with transformer isolation and capacitor coupling to the HART loop. The two HART pins can be connected directly to the loop without concern for polarity. The HART loop resistor, typically 250 ohms, is not included but is required. The TXD, RXD, and DE I/O pins are compatible with 3.3-volt logic, and the module requires an external 3.3-volt power supply connected to VDD.

HART Modem Mode
InLink-HM ships are configured to function as a typical HART protocol modem and are compatible with most HART configuration and test software. Included on the CD are the PACTware FDT frame, HART Protocol DTM, and Microflex Generic DTM software. For information on installing PACTware and the DTM, please reference the PACTware Quick Start Guide. Also included is a HART device addressing utility, which can be used to configure the polling address in HART devices for multi-drop systems.

To function as a HART protocol modem, the module is typically configured for 1200 baud, odd parity, with modbus register filling disabled. When set to use higher baud rates, InLink-HM will receive the HART command at the higher baud rate and then transmit through the modem at 1200 baud odd parity. The HART reply packet is received by the InLink-HM modem and then transmitted back at the higher baud rate on the RXD output pin. HART packets must be formatted in the standard format and include the “FF” preamble characters. If InLink-HM receives “FF” (hex) as the first byte in a new packet, it is assumed to be a HART packet, and InLink will switch to the HART modem mode and stop filling Modbus registers if enabled. If no HART commands are received over the serial port after 30 seconds, InLink-HM will return to polling and filling modbus registers. Also, if a Modbus command is received, InLink will exit HART mode and return to polling and filling Modbus registers. Modbus packets begin with the slave address or universal address 0, but never FF (hex).

Fill Modbus Registers Mode
InLink-HM can be configured to continuously poll a HART loop of 1 to 16 HART devices and fill Modbus registers with HART device variable data – up to 4 variables per device. When enabled, the module will work through a list of HART device polling addresses and use HART command 3 to read the primary, secondary, tertiary, quaternary variables, as well as the loop current. Values are saved in 16-bit signed registers and single-precision floating point (two 16-bit registers per floating point value). The register values can then be read using Modbus command 3. Registers can be grouped by HART device or variable type.

Konfigurace
The InLink-HM configuration is set using a few Modbus setup registers. Refer to the Setup Registers section in this manual for details. The configuration can also be changed using the Microflex HM Configuration program running on a Microsoft Windows PC. The InLink-HM module will need to be connected to a PC serial port to use the HM Configuration software. This can be done using the InLink evaluation board (part number 101-0003). Microflex also offers the InLink-HM Evaluation Board RS-485 (part number 101-0093). InLink-HM Evaluation Board RS-485 includes the necessary RS-485 half duplex transceivers to connect the InLink-HM module to an RS-485 network bus.

Power Supply – 3.3V / GND
InLink-HM requires an external 3.3 volt DC power supply (3.6 volts max). When using the InLink evaluation board, a 3.3-volt supply should be used. To prevent any noise interference to the HART modem, the power supply should be heavily filtered and decoupled to ground. Typical supply current is less than 5 mA. Wait at least 25 milliseconds after powering on before starting any communications transactions.

Serial Port – TXD / RXD
The InLink-HM serial port uses 3.3-volt CMOS logic levels. The InLink evaluation board (101-0003) provides the transceivers necessary to connect the module directly to an RS-232 serial port. The TXD and RXD lines will typically connect to microcontroller IO pins in your OEM application.

Driver Enable – DE
The Driver Enable pin is a Digital Output, Active High. A logic high indicates that a HART or Modbus reply packet is being shifted out serially on RXD. DE can be used for RS-485 transceiver direction control. Firmware version 6 or higher is required for Driver Enable (DE) functionality.

HART Loop – HART
These two pins connect to the HART loop. The internal modem includes transformer isolation, AC capacitor coupling, and line transient protection. The two pins are designed to connect directly to a HART protocol loop. Connections can be made across the HART 230 to 600 ohm loop resistor or across the HART device. All HART loops are required to have a loop resistor.

HART Device Polling Address

Each HART device has a polling address. By default, devices are set to use polling address 0 with the current output enabled. Before a HART master can send commands to a device, it must first use the polling address to learn the unique 5-byte device address. HART command 0 is sent with the polling address set to 0. The HART device replies with a packet that includes the necessary information to build the 5-byte-long address. With the long address learned, the HART master can then send any other HART command to the device.
For multi-drop loops where more than one HART device is in the same loop, each HART device must be set to have a unique polling address. For HART version 3 – 5, the polling address for multi-drop devices can be 1 to 15. For HART version 6 and higher devices, the polling address can be 1 to 63. In multi-drop mode, the current output is set to a fixed value and cannot be used for a process value.

Setting the HART Device Address
HART command 6 is used to set the device’s polling address. The HART host must first use command 0 to learn the long address. The device polling address should only be changed on a HART device that is not controlling or measuring a live process, since the change may alter the current output as well as interfere with a HART master’s ability to communicate with the device. The configuration software for your HART device should include the capability to set the device’s polling address. The Microflex HART Host app includes the capabilities to scan for and change a device’s HART address.

InLink-HM HART – Modbus Accumulator

In addition to being a HART Protocol Modem module, the InLink HM can be set to collect and store process variable information from up to 16 HART devices. HART devices are continuously polled, and variable information is accumulated into a table of Modbus registers. Using the InLink Evaluation Board serial port, the registers can be read using Modbus RTU command 3. Variable data can be read as 16-bit integers or 32-bit floating point. Up to 4 variables for each polled HART device.
In the accumulate mode, InLink-HM will function as a HART master (primary or secondary) polling devices and storing variable values into registers. No additional HART software is needed. The HART loop may contain a single device or up to 16 devices. When more than one device is in the loop, each HART device must have a unique HART polling address. The address for each device is set before wiring the device into the multi-drop loop. The device polling address for each device is stored in the InLink-HM using the HM Configuration Software.
Modbus slave address, baud rate, parity, and other settings are set using the HM Configuration Software. Configuration is done using the same port that Modbus will use, so no additional setup cable is required. After the configuration is completed, the port is connected to the Modbus controller. Upon powering on, the InLink-HM will begin polling and accumulating values. Modbus RTU command 3 is used to read the accumulated values.

HM Configuration Software Installation – Windows

The HM-Configurator software is used to configure the MicroLink-HM serial port and Modbus accumulator mode. All of the configuration settings are saved in Modbus registers and can also be set using Modbus RTU command 6 or 16. Details, including register definitions, are included in the Installation, Operation, and Specification manual. The MicroLink-HM can be connected directly to a Windows PC RS-232 serial port or a USB-to-serial converter cable.

Instalace
Download the HM-Configurator app from
https://microflx.com/products/hm-configuration-software-app

Microflex InLink HM 101 0014 HART Protocol Modem Module - Symbol 1

Spusťte stažené file to install the HM-Configurator.
After Installation, the HM Configurator icon will be added to your system.

Domovská obrazovka

The home screen displays a summary of the HM Configuration status, HART modem settings, and Modbus settings. Use the top drop-down menus to configure the InLink-HM modem.

Set up the COM Port
The HM Configuration software must be set to use the same COM port that the modem is connected to. From the top menu, select Setup>Com Port. Choose the COM port number from the list of available ports. After choosing, click Connect to attempt to connect using the settings selected. The connection process will first try the last good baud rate and parity settings. If it fails to connect, the process will work through other settings to try to find the correct InLink-HM settings for communications. If it still does not connect, verify that you have chosen the correct COM number, connections are correct, and power is on before trying again.

Microflex InLink HM 101 0014 HART Protocol Modem Module - Home Screen

HART Protocol Settings

With Fill Modbus Registers unchecked, InLink-HM will function as a standard HART protocol modem and not poll HART devices to fill Modbus registers. In this mode, HART packets are received and then retransmitted at the HART 1200 baud, odd parity. Received reply packets are retransmitted at the selected baud rate. RTS timing and carrier detection are handled internally by the InLink-HM, allowing communications at higher than 1200 baud. HART loop data is handled at the standard HART protocol 1200 baud, odd parity, but because InLink-HM buffers the data, the port can be set for higher rates as well as odd, even, or no parity. Port settings can be set in the Modbus Settings section.

Microflex InLink HM 101 0014 HART Protocol Modem Module - HART Protocol Settings

Since InLink-HM manages network timing, it needs to be configured for either a primary or secondary master. Configuration modems are typically set to be secondary masters.

Polling HART Devices – Fill Modbus Registers

To enable Modbus register accumulation, check the Fill Modbus Registers option. The Hart Protocol Settings window will expand to show the Polled Devices settings.

Opakování
If a HART device is polled but does not respond, or errors are detected, InLink-HM can retry up to 3 times before indicating a bad device. If a device is not responding, the Modbus values are filled with Hart Device Failed register values – setup is done in the Modbus configuration section.

Polled Devices
V example screenshot (Figure 5), InLink-HM is set to poll one HART device using polling address 0 and will retry 1 time before reporting a communications error. The Device Variables (Modbus Register Values) box on the right displays the register values for the active polled device. Click Add Device to add a polled HART device. Be sure to set the Polling Address for each device. Each device must have a unique HART polling address. Polling addresses must be set up for each HART device before it can be connected to a multi-drop HART loop, and can be set from 1 to 63.
Address O can only be used when one device is in the HART loop.
Polling addresses 16-63 should only be used with HART revisions 6 and higher. For HART 3-5, use addresses 1-15 for multi-drop systems.

Microflex InLink HM 101 0014 HART Protocol Modem Module - Polled DevicesFigure 5. HART protocol settings dialog when filling Modbus registers is enabled.

Desetinná místa
When device data is stored in a 16-bit signed Modbus register, the value can range from -32768 to 32767. To allow the 16-bit integer to represent a smaller number and include fractional information, the number of decimal places is stored in a separate Modbus register and applied later. The number of decimal places can be set from 0 to 5. Decimal places can be set for each variable. The Device Variables box shows the effect of the decimal place setting. Decimal place settings are not used for the Modus floating point register values.

Modbus – RTU Setup

Modbus-RTU Settings can be accessed and changed by clicking Setup>Modbus from the top drop-down menu.

Microflex InLink HM 101 0014 HART Protocol Modem Module - Modbus seƫ ngs dialogFigure 6. Modbus settings dialog.

Adresa Modbus
Each device on a Modbus network must have a unique address. Set this to match the address that your Modbus master will use to communicate with the InLink-HM. The Modbus address can be set to any value from 1 to 247. The HM Configuration software will discover this address as part of the connection process.

Baud Rate & Parity
The InLink-HM baud rate and parity must be set to the same settings as your Modbus master. If you are using the InLink-HM as a HART protocol modem, these should be set to 1200 baud, odd parity. Click Use HART Protocol Settings to set the correct values for a HART modem.

Holding Registers Map
Accumulated data is stored in Modbus registers that are grouped or mapped by HART device or by variable type. Choose the register map that best fits your application. Register maps can be viewed using the HM Configuration software. From the top drop-down menu, select View -> Modbus Registers Maps (Figure 7).

Floating Point Byte Order
Modbus 32-bit floating point numbers are stored in two consecutive 16-bit registers using the IEEE-754 standard big endian byte order (AB-CD). The most significant byte (A) is sent first. For compatibility with some Modbus systems, you may need to use the word-swapped format (CD-AB).

HART Device Failed Register Value
If a polled HART device fails to respond or has communications errors, it will retry for the number of times set in the HART Protocol Settings dialog. If, after retries, the device does not respond, you can choose to hold the last value, set to a preset number, or set to the IEEE-754 NaN floating point value. This can help the Modbus master determine when a HART device is no longer responding.

Obnovit výchozí

To restore InLink-HM to its default settings, select Setup>Restore Defaults from the top drop-down menu. This functionality requires HM Configurator Software 1.2.0.5 or higher.

Microflex InLink HM 101 0014 HART Protocol Modem Module - Menu for viewing modbus register mapsFigure 7. Menu for viewing Modbus register maps.

Setup Registers

The InLink-HM configuration can be changed using the setup and configuration software or by writing to Modbus registers using Modbus-RTU commands 6 or 16. Command 6 writes to a single register, and command 16 writes to a range of Modbus registers. The configuration register values are saved in nonvolatile memory and are not lost when InLink-HM power is removed.

Modbus Register Description (high byte, low byte)
772 HART Failed Code Preset Value
773 HART Mode Settings
774 Nastavení Modbus
775 Modbus Port Settings
776 Hardware Rev, Software Rev
777 Polled device status

HART Settings

Microflex InLink HM 101 0014 HART Protocol Modem Module - HART Settings

Bits 9, 8 HART failed mode. 0 = Hold last value after HART retries
1 = Preset to register 772 value after HART retries
2 = Preset to IEEE-754 NaN (0 for integers)
Bits 7, 6 HART poll retries. Sets the number of HART device poll retries from 1 to 3. After poll retries, the HART failed mode value is stored in the variable register.
Bits 3 – 0 Number of polled devices – 1  Range is 0 to 15. 0 = 1 polled device. 15 = 16 polled devices.

Nastavení režimu

Microflex InLink HM 101 0014 HART Protocol Modem Module - Mode Settings

Bit 9 – Floating point value byte order 0 = Standard byte order (AB – CD)
1 = Swapped words (CD – AB)
Bit 8 – Modbus device map 0 = Map register data by HART device
1 = Map register data by variable type

Nastavení sériového portu

Bits 13, 12
00 = Žádná parita
01 = sudý
10 = liché

Bits 11 – 8

1 = 1200 Baud
2 = 2400
3 = 4800
4 = 9600
5 = 14400
6 = 19200
7 = 38400
8 = 57600
9 = 115200

Microflex InLink HM 101 0014 HART Protocol Modem Module - Serial Port Settings

Polled HART Devices Long Address Table

Device ID information is read from each polled device using the device’s polling address and HART command 0. The reply to command 0 for each polled device is used to populate the long address table. When InLink-HM needs to poll for the device variables, using HART command 3, this table holds the information needed to build the 5-byte long address. Table values can be read using Modbus-RTU command 3. Only the polled device you have configured will contain valid information. The table is updated after each valid device poll.

JELEN
Zařízení
Modbus
Rejstřík
Description (high byte, low byte)
1 700 Preambles, Man. Code or Type
701 Device Type, ID 1
702 ID 2, ID3
2 703 Preambles, Man. Code or Type
704 Device Type, ID 1
705 ID 2, ID3
3 706 Preambles, Man. Code or Type
707 Device Type, ID 1
708 ID 2, ID3
4 709 Preambles, Man. Code or Type
710 Device Type, ID 1
711 ID 2, ID3
5 712 Preambles, Man. Code or Type
713 Device Type, ID 1
714 ID 2, ID3
6 715 Preambles, Man. Code or Type
716 Device Type, ID 1
717 ID 2, ID3
7 718 Preambles, Man. Code or Type
719 Device Type, ID 1
720 ID 2, ID3
8 721 Preambles, Man. Code or Type
722 Device Type, ID 1
723 ID 2, ID3
9 724 Preambles, Man. Code or Type
725 Device Type, ID 1
726 ID 2, ID3
10 727 Preambles, Man. Code or Type
728 Device Type, ID 1
729 ID 2, ID3
11 730 Preambles, Man. Code or Type
731 Device Type, ID 1
732 ID 2, ID3
12 733 Preambles, Man. Code or Type
734 Device Type, ID 1
735 ID 2, ID3
13 736 Preambles, Man. Code or Type
737 Device Type, ID 1
738 ID 2, ID3
14 739 Preambles, Man. Code or Type
740 Device Type, ID 1
741 ID 2, ID3
15 742 Preambles, Man. Code or Type
743 Device Type, ID 1
744 ID 2, ID3
16 745 Preambles, Man. Code or Type
746 Device Type, ID 1
747 ID 2, ID3

HART Device Polling Address Table

The polling address for each polled device is stored in this table. Two polling addresses in each 16-bit register. If address 0 is used, then only one device can be polled, and Device 1 should be set to 0. Address 0 is not valid in multi-drop systems. For HART devices with HART revision 3 through 5, you should use polling addresses 1 – 15. Addresses 16-63 require HART revision 6 or higher.

Modbus
Rejstřík
HART Device Polling Address (high byte, low byte)
748 Device 1, Device 2
749 Device 3, Device 4
750 Device 5, Device 6
751 Device 7, Device 8
752 Device 9, Device 10
753 Device 11, Device 12
754 Device 13, Device 14
755 Device 15, Device 16

Number of Decimal Places Table

When storing the HART variable data in 16-bit Modbus registers, the maximum range is -32768 to 32767. To increase the possible resolution, the variable value read from the HART device is decimal position adjusted before being saved in the 16-bit register. When the register is read, the value must be corrected by the number of decimal places to produce the correct value. The number of decimal places for each variable occupies 4 bits in the register, with one register for each polled device.

Desetinná čísla Variabilní rozsah
0 -32768 až 32767
1 -3276.8 až 3276.7
2 -327.68 až 327.67
3 -32.768 až 32.767
4 -3.2768 až 3.2767
5 -0.32768 až 0.32767
JELEN
Zařízení
Modbus
Rejstřík
Počet desetinných míst
Description (high byte, low byte)
1 756 PV−SC, TV−FV
2 757 PV−SC, TV−FV
3 758 PV−SC, TV−FV
4 759 PV−SC, TV−FV
5 760 PV−SC, TV−FV
6 761 PV−SC, TV−FV
7 762 PV−SC, TV−FV
8 763 PV−SC, TV−FV
9 764 PV−SC, TV−FV
10 765 PV−SC, TV−FV
11 766 PV−SC, TV−FV
12 767 PV−SC, TV−FV
13 768 PV−SC, TV−FV
14 769 PV−SC, TV−FV
15 770 PV−SC, TV−FV
16 771 PV−SC, TV−FV

Modbus Register Map – Grouped by HART Device

Rejstřík Popis
7 Loop Current Integer
254, 255 Loop Current Float

Zařízení 1

Rejstřík Popis
0 PV Integer
1 SV Integer
2 TV Integer
3 FV Integer
4 Stav HART
5 MSB = PV UOM, LSB = SV UOM
6 MSB = TV UOM, LSB = FV UOM
256, 257 PV Float
258, 259 SV Float
260, 261 TV Float
262, 263 FV Float

Zařízení 2

8 PV Integer
9 SV Integer
10 TV Integer
11 FV Integer
12 Stav HART
13 MSB = PV UOM, LSB = SV UOM
14 MSB = TV UOM, LSB = FV UOM
264, 265 PV Float
266, 267 SV Float
268, 269 TV Float
270, 271 FV Float

Zařízení 3

16 PV Integer
17 SV Integer
18 TV Integer
19 FV Integer
20 Stav HART
21 MSB = PV UOM, LSB = SV UOM
22 MSB = TV UOM, LSB = FV UOM
272, 273 PV Float
274, 275 SV Float
276, 277 TV Float
278, 279 FV Float

Zařízení 4

Rejstřík Popis
24 PV Integer
25 SV Integer
26 TV Integer
27 FV Integer
28 Stav HART
29 MSB = PV UOM, LSB = SV UOM
30 MSB = TV UOM, LSB = FV UOM
280, 281 PV Float
282, 283 SV Float
284, 285 TV Float
286, 287 FV Float

Zařízení 5

32 PV Integer
33 SV Integer
34 TV Integer
35 FV Integer
36 Stav HART
37 MSB = PV UOM, LSB = SV UOM
38 MSB = TV UOM, LSB = FV UOM
288, 289 PV Float
290, 291 SV Float
292, 293 TV Float
294, 295 FV Float

Zařízení 6

40 PV Integer
41 SV Integer
42 TV Integer
43 FV Integer
44 Stav HART
45 MSB = PV UOM, LSB = SV UOM
46 MSB = TV UOM, LSB = FV UOM
296, 297 PV Float
298, 299 SV Float
300, 301 TV Float
302, 303 FV Float

Zařízení 7

Rejstřík Popis
48 PV Integer
49 SV Integer
50 TV Integer
51 FV Integer
52 Stav HART
53 MSB = PV UOM, LSB = SV UOM
54 MSB = TV UOM, LSB = FV UOM
304, 305 PV Float
306, 307 SV Float
308, 309 TV Float
310, 311 FV Float

Zařízení 8

56 PV Integer
57 SV Integer
58 TV Integer
59 FV Integer
60 Stav HART
61 MSB = PV UOM, LSB = SV UOM
62 MSB = TV UOM, LSB = FV UOM
312, 313 PV Float
314, 315 SV Float
316, 317 TV Float
318, 319 FV Float

Zařízení 9

64 PV Integer
65 SV Integer
66 TV Integer
67 FV Integer
68 Stav HART
69 MSB = PV UOM, LSB = SV UOM
70 MSB = TV UOM, LSB = FV UOM
320, 321 PV Float
322, 323 SV Float
324, 325 TV Float
326, 327 FV Float

Zařízení 10

Rejstřík Popis
72 PV Integer
73 SV Integer
74 TV Integer
75 FV Integer
76 Stav HART
77 MSB = PV UOM, LSB = SV UOM
78 MSB = TV UOM, LSB = FV UOM
328, 329 PV Float
330, 331 SV Float
332, 333 TV Float
334, 335 FV Float

Devicer 11

80 PV Integer
81 SV Integer
82 TV Integer
83 FV Integer
84 Stav HART
85 MSB = PV UOM, LSB = SV UOM
86 MSB = TV UOM, LSB = FV UOM
336, 337 PV Float
338, 339 SV Float
340, 341 TV Float
342, 343 FV Float

Zařízení 12

88 PV Integer
89 SV Integer
90 TV Integer
91 FV Integer
92 Stav HART
93 MSB = PV UOM, LSB = SV UOM
94 MSB = TV UOM, LSB = FV UOM
344, 345 PV Float
346, 347 SV Float
348, 349 TV Float
350, 351 FV Float

Zařízení 13

Rejstřík Popis
96 PV Integer
97 SV Integer
98 TV Integer
99 FV Integer
100 Stav HART
101 MSB = PV UOM, LSB = SV UOM
102 MSB = TV UOM, LSB = FV UOM
352, 353 PV Float
354, 355 SV Float
356, 357 TV Float
358, 359 FV Float

Zařízení 14

104 PV Integer
105 SV Integer
106 TV Integer
107 FV Integer
108 Stav HART
109 MSB = PV UOM, LSB = SV UOM
110 MSB = TV UOM, LSB = FV UOM
360, 361 PV Float
362, 363 SV Float
364, 365 TV Float
366, 367 FV Float

Zařízení 15

Rejstřík Popis
112 PV Integer
113 SV Integer
114 TV Integer
115 FV Integer
116 Stav HART
117 MSB = PV UOM, LSB = SV UOM
118 MSB = TV UOM, LSB = FV UOM
368, 369 PV Float
370, 371 SV Float
372, 373 TV Float
374, 375 FV Float

Zařízení 16

120 PV Integer
121 SV Integer
122 TV Integer
123 FV Integer
124 Stav HART
125 MSB = PV UOM, LSB = SV UOM
126 MSB = TV UOM, LSB = FV UOM
376, 377 PV Float
378, 379 SV Float
380, 381 TV Float
382, 383 FV Float

Modbus Register Map – Grouped by Variable Type

Rev 1

Loop Current − Integer 112
Loop Current − Float 254, 255
16−bit Signed Registers 16−bit Unsigned
JELEN
Zařízení
PV
Celé číslo
SV
Celé číslo
TV
Celé číslo
FV
Celé číslo
JELEN
Postavení
UOM
PV, SV
UOM
TV, FV
1 0 16 32 48 64 80 96
2 1 17 33 49 65 81 97
3 2 18 34 50 66 82 98
4 3 19 35 51 67 83 99
5 4 20 36 52 68 84 100
6 5 21 37 53 69 85 101
7 6 22 38 54 70 86 102
8 7 23 39 55 71 87 103
9 8 24 40 56 72 88 104
10 9 25 41 57 73 89 105
11 10 26 42 58 74 90 106
12 11 27 43 59 75 91 107
13 12 28 44 60 76 92 108
14 13 29 45 61 77 93 109
15 14 30 46 62 78 94 110
16 15 31 47 63 79 95 111
32−bit Float Registers
JELEN
Zařízení
PV
Plovák
SV
Plovák
TV
Plovák
YV
Plovák
1 256, 257 288, 289 320, 321 352, 353
2 258, 259 290, 291 322, 323 354, 355
3 260, 261 292, 293 324, 325 356, 357
4 262, 263 294, 295 326, 327 358, 359
5 264, 265 296, 297 328, 329 360, 361
6 266, 267 298, 299 330, 331 362, 363
7 268, 269 300, 301 332, 333 364, 365
8 270, 271 302, 303 334, 335 366, 367
9 272, 273 304, 305 336, 337 368, 369
10 274, 275 306, 307 338, 339 370, 371
11 276, 277 308, 309 340, 341 372, 373
12 278, 279 310, 311 342, 343 374, 375
13 280, 281 312, 313 344, 345 376, 377
14 282, 283 314, 315 346, 347 378, 379
15 284, 285 316, 317 348, 349 380, 381
16 286, 287 318, 319 350, 351 382, 383

Bezpečnostní aspekty

Microflex InLink HM 101 0014 HART Protocol Modem Module - Symbol 2 Shoda v souladu s částí 2 a částí 15, hlavami A a B Federálních komunikačních pravidel a předpisů a ICES-003 norem Industry Canada.
varování 2 Toto zařízení je v souladu s částí 15 pravidel FCC. Provoz podléhá následujícím dvěma podmínkám: (1) Toto zařízení nesmí způsobovat škodlivé rušení a (2) toto zařízení musí akceptovat jakékoli přijaté rušení, včetně rušení, které může způsobit nežádoucí provoz. Změny nebo úpravy, které nejsou výslovně schváleny společností Microflex, mohou zrušit oprávnění uživatele provozovat toto zařízení.
SYMBOL CE Emise EN55022: 1998
Elektrostatický výboj EN61000-4-2: 1995, A1: 1998, A2: 2001
Vyzařovaná imunita EN 61000-4-3: 2002
Safety Compliance EN 60950-1:2002
varování 2 Toto zařízení nemá ochranu proti přepětítages, which may exist on RS-232 ports of computers, and relies on the protection existing in a host computer.
varování 2 Toto zařízení není určeno pro připojení k telefonní lince přes příslušné převodníky a nesmí být připojeno k telekomunikačním linkám, protože nemá ochranu proti přepětí.tages, které mohou existovat v těchto řádcích.
varování 2 Uživatel zajistí ochranu obsluhy před přístupem do prostor s nebezpečným objtagnebo nebezpečné energie v jejich zařízení.
varování 2 Uživatel musí zajistit, aby připojovací port provozního zařízení a modemu byl oddělen alespoň základní izolací od jakéhokoli primárního okruhu existujícího v provozním zařízení.

Omezená záruka

Microflex, LLC warrants this unit against defects in materials and workmanship for a period of one year from the date of shipment. Microflex, LLC will, at its option, repair or replace equipment that proves to be defective during the warranty period. This warranty includes parts and labor.

Číslo RMA (Return Materials Authorization) musí být získáno z továrny a musí být zřetelně označeno na vnější straně balení, než bude zařízení přijato k záruční práci.

Microflex, LLC, believes that the information in this manual is accurate. In the event that a typographical or technical error exists, Microflex, LLC reserves the right to make changes without prior notice to holders of this edition. The reader should consult Microflex, LLC if any errors are suspected. In no event should Microflex, LLC be liable for any damages arising out of or related to this document or the information contained in it.

S VÝJIMKOU ZDE UVEDENÝCH PŘÍPADŮ SPOLEČNOST MICROFLEX, LLC NEPOSKYTUJE ŽÁDNÉ ZÁRUKY ANI OBCHODOVATELNOSTI ANI VHODNOSTI PRO URČITÝ ÚČEL. PRÁVO ZÁKAZNÍKA NA NÁHRADU ŠKOD ZPŮSOBENÉ ZAVINNĚNÍM NEBO NEDBALOSTI SPOLEČNOSTI MICROFLEX JE OMEZENO NA ČÁSTKU, KTEROU ZÁKAZNÍK PŘEDTÍM ZAPLACIL. SPOLEČNOST MICROFLEX, LLC NEBUDE ODPOVĚDNÁ ZA ŠKODY VYPLÝVAJÍCÍ ZTRÁTOU DAT, ZISKŮ, POUŽITÍM PRODUKTŮ NEBO NÁHODNÝMI NEBO NÁSLEDNÝMI ŠKODAMI, ATO I V PŘÍPADĚ, ŽE BYLA NA MOŽNOSTI JEJICH VZNIKU UPOZORNĚNA. Toto omezení odpovědnosti společnosti Microflex, LLC platí bez ohledu na formu žaloby, ať už smluvní nebo občanskoprávní, včetně nedbalosti. Jakákoli žaloba proti společnosti Microflex, LLC musí být podána do jednoho roku od vzniku důvodu žaloby. Tato záruka se nevztahuje na škody, vady, poruchy ani selhání služby způsobené nedodržením pokynů k instalaci, provozu nebo údržbě společnosti Microflex, LLC ze strany majitele; úpravou produktu ze strany majitele; zneužitím, nesprávným použitím nebo nedbalostním jednáním majitele; a výpadkem proudu nebo přepětím, požárem, záplavou, nehodou, jednáním třetích stran nebo jinými událostmi mimo přiměřenou kontrolu.

Microflex InLink HM 101 0014 HART Protocol Modem Module - Symbol 3

Microfl ex, LLC
Královská cesta 35900
Pa syn, Texas 77423
USA
Telefon 281-855-9639
Fax 832-422-4391
www.microflx.com

Microflex InLink HM 101 0014 HART Protocol Modem Module - QR Codehttp://www.microflx.com/

The HART protocol is supported by the FieldComm Group in Aus and Texas, www.fieldcommgroup.org. HART je registrovaná ochranná známka společnosti FieldComm Group.

Logo Microflex

Dokumenty / zdroje

Microflex InLink-HM 101-0014 HART Protocol Modem Module [pdfNávod k obsluze
101-0014, 101-0003, 101-0093, InLink-HM 101-0014 HART Protocol Modem Module, InLink-HM 101-0014, HART Protocol Modem Module, Protocol Modem Module, Modem Module

Reference

Zanechte komentář

Vaše emailová adresa nebude zveřejněna. Povinná pole jsou označena *