KELD-logo

KELD KLT11IB Temperature Digital Controller

KELD-KLT11IB-Temperature-Digital-Controller-product

Popis

The KLT11IB is designed for heating and cooling applications. The probe temperature is displayed on the bright 3-digit display. The user is able to program different parameters including set point, hysteresis, alarms and probe adjustment using the silicone front keypad. The unit features error or alarm warning, internal buzzer (optional), configurable digital input and password protection. The KLKey input allows an easy programming of the parameters. Select between temperature display in ºC or ºF, display color and 230Vac, 115Vac, 24Vac/dc or 12Vac/dc power supplies.

Reference modelu

The model reference is given by: KLT11IBXYZ Where each sufix can take the following values:

  • X Display Color R=Red, G=Green, B=Blue
  • Objem dodávky Ytage 230=230Vac, 110=115Vac 24=24Vac/dc 12=12Vac/dc
  • Z Units C=ºC, F=ºF

Instalace

  • NOTE: Unit must be mounted away from vibration, impacts, waterand corrosive gases.
  • Cut hole in panel 71 x 29 mm (2.80 x 1.14 inches)
  • Aplikujte silikon (nebo pryžové těsnění) po obvodu otvoru, abyste zabránili úniku.
  • Insert unit into hole of panel.
  • Slide removable fitting clips onto unit from the back until secure to panel.
  • Wiring diagram is displayed on the top of the unit
  • NOTE: DO NOT INSTALL PROBE CABLE NEAR POWER CABLES.

Údržba, čištění a opravy

After final installation of the unit, no routine maintenance is required Clean the surface of the display controller with a soft and damp hadříkem. Nikdy nepoužívejte abrazivní čisticí prostředky, benzín, líh ani rozpouštědla.
Veškeré opravy musí být provedeny autorizovaným personálem.

Schéma zapojení

KELD-KLT11IB-Temperature-Digital-Controller-fig-1

Technická data

  • Napájecí objemtages
    230Vac±10%,115Vac±10%, 24Vac/dc±10%, 12Vac/dc±10%
  • Supply powers
    4VA (230V/115V) 1,5VA(24V /12V)
  • Skladovací teplota
    -20ºC to 80ºC (-4 to 176ºF)
  • Provozní teplota
    0ºC to 60ºC (32 to 140ºF)
  • Rozsah sondy
    -200ºC to 600ºC (-328 to 999ºF)
  • Vstup sondy
    Pt100 (0ºC – 100 Ohm)
  • Přesnost
    Better than ±0,5% of full scale
  • Rezoluce
    0.1º from -99.9ºC to 99.9ºC
    1º out of this range
  • Zobrazit
    3-digit and sign (red, green or blue)
  • Digitální vstup
    svtage bezplatný kontakt
  • Výstup
    SPDT Relay Resistive load 16A
    1HP 240Vac — 10FLA, 60LRA 240Vac
  • KLKey Input
    For an quick programming of all parameters
  • Rozměry
    Front 77 x 36 mm Depth 62 mm (3.03 x 1.42 x 2.44 inch)
  • Přední ochrana
    IP64

Seznam Parametrů

KELD-KLT11IB-Temperature-Digital-Controller-fig-2

Popisy parametrů

  • SP = Set point. Temperature we wish to regulate the machine (variable from r1 to r2)
  • r0 = Differential or hysteresis
  • r1 = Lower value for SP
  • r2 = Higher value for SP
  • r4 = Set point variation for energy saving. If digital input configuration EO = ES this value modify the set point as follows:
    • If do = Ht new SP = SP – r4
    • If do = Co new SP = SP + r4
  • do Cooling or heating control
  • If do = Ht and TS is the temperature of ambient probe:
    • If TS >= SP the load is disconnected
    • If TS <= SP – rO the load is connected
  • If dO = Co then:
    • If TS <= SP the load is disconnected
    • If TS >= SP + r0 the load is connected
  • c0 = Minimum stopping time of the load
  • c2 = Output status with probe error
  • P1 = Ambient probe adjustment
  • P4 = Decimal point
  • P5 = 3 wires Pt100. no = 2 wires, yes = 3 wires
  • E0 = Digital input configuration
  • OFF = Digital input disabled
  • Al = External alarm (if input is short-circuited)
  • ES = Energy Saving. Set Point value is modified in r4.
  • HC = if input is short-circuited, it changes to Heat or Cold depending of the dO value.
    • if dO = Heat it changes to Cold mode.
    • if do = Cold it changes to Heat mode.
  • H5 = Access code to parameters (it is set to 00 from factory)
  • A0, A1, A2, A3 = Alarm 1 parameters
  • Pokud A3=VYP, alarm 1 je deaktivován
  • Pokud A3=HI, nastaví se alarm vysoké teploty:
    • Pokud TS >= SP+A1, aktivuje se alarm 1
    • if TS <= SP+A1-A0 the alarm 1 is deactivated
  • Pokud A3=LO, nastaví se alarm nízké teploty:
    • Pokud TS <= SP-A1, aktivuje se alarm 1
    • if TS >= SP-A1+A0 the alarm 1 is deactivated
  • The alarm 1 is not activated until the time since the instrument is turn on is higher than A2
  • A4, A5, A6, A7 = Alarm 2 parameters (similar to alarm 1)
  • A8 = Alarm verification time. Time since the alarm situation occurs until its signalling. (It affects to Alarm 1, Alarm 2 and External alarm)

Programování parametrů

Nastavená hodnota (SP) je jediný parametr, ke kterému má uživatel přístup bez ochrany kódem.

  • Press SET. SP text will appear on the display.
  • Znovu stiskněte tlačítko SET. Na displeji se zobrazí skutečná hodnota.
  • Hodnotu lze upravit pomocí šipek NAHORU a DOLŮ.
  • Stiskněte SET pro zadání nových hodnot.
  • Stiskněte současně SET a DOWN pro ukončení programování nebo počkejte jednu minutu a displej automaticky opustí programovací režim.

Access to all code-protected parameters.

  • Stiskněte tlačítko SET po dobu 8 sekund. Na displeji se zobrazí přístupový kód 00 (jednotka je dodávána s kódem nastaveným z výroby na 00).
  • Pomocí šipek NAHORU a DOLŮ lze kód nastavit podle potřeb uživatele.
  • Stiskněte tlačítko SET pro zadání kódu. Pokud je kód správný, na displeji se zobrazí první parametr (SP).
  • Pomocí tlačítek NAHORU a DOLŮ přejděte na požadovaný parametr.
  • Stiskněte SET pro view hodnotu na displeji.
  • Hodnotu lze upravit pomocí šipek NAHORU a DOLŮ.
  • Stisknutím tlačítka SET zadejte hodnotu a ukončete nabídku.
  • Opakujte, dokud nezměníte všechny potřebné parametry.
  • Stiskněte současně SET a DOWN pro ukončení programování nebo počkejte jednu minutu a displej automaticky opustí programovací režim.
  • *Kód klávesnice lze vynulovat vypnutím a opětovným zapnutím ovladače se stisknutým tlačítkem SET.

LED indikace, bzučák a zprávy na displeji

  • LED dioda OUT indikuje, zda je zátěž připojena či nikoli.
  • In normal operation, the probe temperature will be shown on the display.
  • In case of alarm or error, the following messages can be shown (the alarm led is ON and buzzer sounds):
    • Err = Chyba paměti.
    • ooo = Chyba otevřené sondy.
    • — = Short-circuit Probe Error.
    • A1H = Alarm vysoké teploty 1.
    • A1L = Low temperature alarm 1.
    • A2H= Alarm vysoké teploty 2.
    • A2L = Low temperature alarm 2.
    • ALE = Externí alarm.

Ověření alarmu
In case of alarm the internal buzzer and alarm led is activated. The display shown the corresponding message. The buzzer and display message can be silenced pressing the SET and DOWN arrows at the same time. If alarm continues after A8 it is signalling again.

KELD-KLT11IB-Temperature-Digital-Controller-fig-3

Telefon: 551-574-6806
E-mail: service@culimerequipment.com
Web: https://www.culimerequipment.com/

FAQ

  • Q: Is routine maintenance required for the KLT11IB Temperature Digital Controller?
    A: No, after the final installation, no routine maintenance is needed.
  • Q: What should I do for cleaning the controller’s surface?
    A: Clean the surface with a soft and damp cloth. Avoid abrasive detergents, petrol, alcohol, or solvents.
  • Q: What is the output capacity of the controller?
    A: The output is a SPDT relay for resistive loads up to 16A 1HP 240Vac.

Dokumenty / zdroje

KELD KLT11IB Temperature Digital Controller [pdfNávod k obsluze
KLT11IBXYZ X Display Color, Y Supply Voltage, Z Units, KLT11IB Temperature Digital Controller, KLT11IB, Temperature Digital Controller, Digital Controller, Controller

Reference

Zanechte komentář