This manual provides essential information for the proper installation, operation, and maintenance of the NOTIFIER FS-OSI-RI Adressable Beam Detector. The FS-OSI-RI is a sophisticated fire safety device designed to detect smoke over large areas by projecting and receiving an infrared beam. It is an integral component of an addressable fire alarm system, providing reliable early warning capabilities.

2. Bezpečnostní informace

Read all instructions carefully before installation and operation. This device must be installed by qualified personnel in accordance with all local and national electrical and fire codes. Disconnect power before servicing. Failure to follow these instructions may result in property damage, injury, or death. Regular testing and maintenance are crucial for optimal performance.

3. Nastavení

3.1 Vybalení

Carefully remove the beam detector and its components from the packaging. Inspect all items for any signs of damage. Report any damage to your supplier immediately. Retain packaging for future transport or storage.

3.2 Montáž

The FS-OSI-RI consists of a transmitter/receiver unit and a reflector. Mount the transmitter/receiver unit and the reflector on a stable surface, ensuring they are aligned and within the specified operating distance. Refer to the detailed mounting diagrams provided in the separate installation guide for precise placement and alignment procedures. Ensure the mounting location is free from obstructions and excessive vibration.

NOTIFIER FS-OSI-RI Adressable Beam Detector unit

Image 1: The NOTIFIER FS-OSI-RI Adressable Beam Detector unit. This image shows the main component of the beam detector, which houses both the infrared transmitter and receiver. It is typically mounted on a wall or ceiling, facing the reflector.

3.3 Zapojení

Connect the detector to the addressable fire alarm control panel (FACP) using appropriate wiring methods as specified in the FACP manual and local codes. Ensure correct polarity and secure all connections. The device operates on a low-voltage power source provided by the FACP.

3.4 Initial Power-Up and Addressing

After all wiring is complete and verified, apply power to the FACP. The detector will perform a self-test. Set the unique address for the FS-OSI-RI using the addressing mechanism on the device, following the FACP's programming instructions. Proper addressing is critical for the FACP to identify the detector's location and status.

4. Provoz

4.1 Základní funkce

The FS-OSI-RI continuously monitors the infrared beam path between its transmitter/receiver unit and the reflector. When smoke enters the beam path, it obscures the beam, causing a reduction in the received signal. If the signal reduction exceeds a pre-set threshold for a specified duration, the detector will signal an alarm condition to the FACP.

4.2 Stavové indikátory

The detector features LED indicators to communicate its operational status:

  • Zelená LED: Označuje normální provoz.
  • Červená LED: Označuje stav alarmu.
  • Žlutá LED: Indicates a trouble condition (e.g., beam blockage, misalignment, fault).

4.3 Integrace systému

As an addressable device, the FS-OSI-RI communicates its status directly to the FACP, allowing for precise identification of the alarm or trouble source. The FACP will then initiate appropriate responses, such as activating alarms, notifying emergency services, or displaying the event location.

5. Údržba

5.1 Čištění

Periodically inspect the detector's lens and the reflector for dust, dirt, or other obstructions. Clean these surfaces using a soft, lint-free cloth. For stubborn dirt, a mild, non-abrasive cleaning solution may be used, applied to the cloth, not directly to the device. Ensure the device is powered down before cleaning.

5.2 Testing Procedures

Regular functional testing is essential. Perform tests in accordance with NFPA 72 and local authority having jurisdiction (AHJ) requirements. Testing typically involves:

  • Smoke Obscuration Test: Introduce an approved test smoke into the beam path to verify alarm activation.
  • Kontrola zarovnání: Verify proper beam alignment using the detector's alignment indicators or a dedicated alignment tool.
  • Test citlivosti: If applicable, verify the detector's sensitivity settings are within acceptable ranges.

5.3 Výměna baterie

While the primary power source is typically wired, some systems may incorporate backup batteries. If your system includes a battery backup for the detector or its associated control module, ensure batteries are replaced according to the manufacturer's recommendations or when a low battery trouble signal is indicated by the FACP.

6. Řešení problémů

Refer to the FACP manual for specific trouble codes and detailed troubleshooting steps. Below are general troubleshooting guidelines:

  • Falešné poplachy: Check for environmental factors such as dust, steam, insects, or direct sunlight interfering with the beam path. Verify proper alignment and cleanliness of the lens and reflector.
  • Bez detekce: Ensure the detector is powered, correctly addressed, and properly aligned. Check for complete beam obstruction or damage to the unit/reflector.
  • Trouble Signal (Yellow LED): This often indicates a beam blockage, misalignment, or a fault within the unit. Re-align the beam, clean the optics, and check wiring connections. If the issue persists, contact technical support.
  • Chyby komunikace: Verify wiring integrity between the detector and the FACP. Check the detector's address setting.

7. Specifikace

FunkceSpecifikace
Číslo modeluFS OSI RI
Číslo díluNFSOSIRI
VýrobceOZNAMOVATEL
Zdroj napájeníBattery Powered (typically system-level backup or low-voltage from FACP)
Typ alarmuAudible (via FACP)
StylBezpečnost
UPC742779301956

8. Záruka a podpora

For warranty information, please refer to the documentation provided with your purchase or contact your authorized Notifier distributor. Technical support is available through your installer or Notifier's official support channels. Do not attempt to repair the device yourself, as this may void the warranty and compromise safety.

Související dokumenty - FS OSI RI

Předview Návod k instalaci a údržbě detektoru kouře Notifier DHX-501 do vzduchovodu
Tato příručka obsahuje podrobné postupy instalace, zapojení, testování a údržby pouzdra inteligentního vzduchovodního detektoru kouře Notifier DHX-501. Zahrnuje obecné popisy, seznamy součástí, bezpečnostní varování, postupnou instalaci, pravidelnou údržbu a specifikace pro použití s ​​hlásiči Notifier CPX-551 a SDX-551.
Předview Konvenční jednostranný reflexní zobrazovací detektor kouře OSI-R-SS a OSI-RA-SS
Notifier OSI-R-SS a OSI-RA-SS jsou pokročilé konvenční jednopólové reflexní zobrazovací detektory kouře určené pro velké otevřené prostory s vysokými stropy. Nabízejí intuitivní nastavení, odolnost vůči pohybu budovy a slunečnímu záření, automatické nastavení citlivosti a kompenzaci driftu, díky čemuž jsou ideální pro sklady, atria a sportovní arény.
Předview Datový list inteligentního adresovatelného požárního poplachového systému Notifier NFS-320
Komplexní datový list pro inteligentní adresovatelný požární poplašný systém Notifier NFS-320 s podrobným popisem jeho funkcí, inteligentních senzorů, protokolu FlashScan, specifikací systému, kompatibilních zařízení a schválení příslušných úřadů.
Předview Notifier 30-3003 Explosion-Proof Smoke Detector: Features and Specifications
Discover the features, applications, and technical specifications of the Notifier 30-3003 Explosion-Proof Smoke Detector, designed for hazardous industrial environments.
Předview Notifier Intelligent VESDA-E VEU SLC with VESDAnet Detectors | Honeywell
Comprehensive technical data sheet for Notifier Intelligent VESDA-E VEU SLC with VESDAnet detectors (VEU-A00-NTF-VN, VEU-A10-NTF-VN). Learn about Flair detection technology, UL 268 7th Edition compliance, connectivity, modes of operation, specifications, and integration with Honeywell fire alarm control panels.
Předview Ústředna požárního poplachu Notifier AFP-2800: Manuál pro obsluhu, instalaci a programování
Komplexní manuál k ústředně požárního poplachu Notifier AFP-2800, zahrnující návod k obsluze, postupy instalace, programování, popis systému, specifikace a řešení problémů. Nezbytný pro nastavení a údržbu systému.