Zavedení
This manual provides essential information for the installation, operation, and maintenance of the Ranco O10-1402 Low Pressure Control. Please read this manual thoroughly before attempting to install or operate the device to ensure safe and efficient performance.
Konec produktuview
The Ranco O10-1402 is a single-pressure control switch designed to open on low pressure. Its primary function is to protect compressors against loss of refrigerant in commercial refrigeration and air conditioning systems. It is also utilized for cycling compressors in various commercial refrigeration applications.
Mezi klíčové vlastnosti patří:
- Adjustable differential and range for precise control.
- Vysoký-amp rated SPST (Single Pole, Single Throw) switch design.
- Compatible with refrigerants R12, R22, R134A, and R502.
- Easy-to-read scale plate for setting adjustments.

Obrázek 1: Přední strana view of the Ranco O10-1402 Low Pressure Control, showing the pressure scale and Ranco logo.
Specifikace
| Atribut | Hodnota |
|---|---|
| Položka | Ovládání jedním tlakem |
| Typ | Nízký tlak |
| Typ přepínače | SPST |
| Přepnout akci | Opens On Low Pressure |
| Rozsah tlaku (PSI) | (12") to 50 (0.4 to 3.5 bar) |
| Differential Pressure (PSI) | 5 to 35 (0.3 to 2.4 bar) |
| Resetovat | Auto |
| Tlakové připojení | 36" Capillary with 1/4" Flare Nut |
| Capillary Length (In.) | 36 |
| Montáž | Universal / Panel Mount |
| Příloha | NEMA 1 |
| Provozní režim | Automatický |
| Typ kontaktu | Normálně zavřeno |
| Kontaktní materiál | Kov |
| Rozměry produktu | 9 x 7 x 5 palce |
Nastavení a instalace
Proper installation is crucial for the safe and effective operation of the Ranco O10-1402. It is recommended that installation be performed by a qualified technician.
Montáž
The control features universal mounting capabilities. Ensure the mounting surface is stable and free from excessive vibration. Use appropriate fasteners for secure attachment.

Figure 2: Ranco O10-1402 Low Pressure Control shown with its mounting bracket and installation accessories, including screws and instructions.
Tlakové připojení
- Connect the 36-inch copper capillary tube with the 1/4" flare nut to the low-pressure side of the refrigeration system.
- Ensure all connections are tight to prevent refrigerant leaks. Use appropriate sealing compounds if necessary.

Obrázek 3: Zadní view of the Ranco O10-1402, highlighting the capillary tube connection point.
Elektrické rozvody
The control features an SPST switch. Refer to the wiring diagram provided with your specific system or consult a qualified electrician for proper electrical connections. Ensure power is disconnected before wiring.

Obrázek 4: Vnitřní view of the Ranco O10-1402 with the cover removed, showing the electrical terminals and adjustment mechanism.
Návod k obsluze
Setting Pressure Range and Differential
The Ranco O10-1402 allows for adjustment of both the pressure range and differential. These settings determine the cut-in and cut-out points of the compressor.
- Úprava rozsahu: Use a screwdriver to adjust the main pressure setting. The scale plate indicates the pressure at which the switch will open (cut-out).
- Nastavení diferenciálu: Adjust the differential setting to determine the pressure difference between the cut-out and cut-in points. The cut-in pressure will be the cut-out pressure plus the differential.
- Refer to your system's specifications for recommended pressure and differential settings.

Obrázek 5: Detail view of the Ranco O10-1402's front panel, detailing the pressure scale and the adjustment screw for setting the control parameters.
The control is designed for automatic reset, meaning it will automatically close (cut-in) once the pressure rises above the set cut-out pressure plus the differential.
Údržba
The Ranco O10-1402 Low Pressure Control is designed for reliable operation with minimal maintenance. However, periodic checks are recommended to ensure continued performance.
- Vizuální kontrola: Regularly inspect the control for any signs of physical damage, corrosion, or loose connections.
- Kapilární trubice: Check the capillary tube for kinks, damage, or leaks. Ensure it is securely fastened and not exposed to excessive heat or sharp objects.
- Elektrické připojení: Zkontrolujte, zda jsou všechna elektrická připojení bezpečná a bez koroze.
- Čištění: Keep the exterior of the control clean and free from dust and debris. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.
Poznámka: Any internal repairs or adjustments beyond the specified range and differential settings should only be performed by qualified service personnel.
Odstraňování problémů
Tato část obsahuje pokyny pro řešení běžných problémů. V případě složitých problémů se obraťte na kvalifikovaného technika.
| Problém | Možná příčina | Řešení |
|---|---|---|
| Compressor not cycling | Incorrect pressure setting; Faulty wiring; Low refrigerant charge. | Verify pressure and differential settings; Check electrical connections; Inspect refrigerant levels. |
| Control not responding to pressure changes | Damaged capillary tube; Internal control failure. | Inspect capillary tube for damage or kinks; If tube is intact, control may need replacement. |
| Nepravidelný provoz | Vibration; Loose connections; Contamination. | Ensure secure mounting; Tighten all connections; Clean control exterior. |
Záruka a podpora
For warranty information or technical support regarding your Ranco O10-1402 Low Pressure Control, please contact the manufacturer, CAI - RANCO, or your authorized distributor. Keep your purchase receipt and model number (O10-1402) readily available when seeking support.
Manufacturer: CAI - RANCO
Date First Available: September 24, 2018