This manual provides essential information for the installation, operation, and maintenance of the Ranco O10-1402 Low Pressure Control. Please read this manual thoroughly before attempting to install or operate the device to ensure safe and efficient performance.

Konec produktuview

The Ranco O10-1402 is a single-pressure control switch designed to open on low pressure. Its primary function is to protect compressors against loss of refrigerant in commercial refrigeration and air conditioning systems. It is also utilized for cycling compressors in various commercial refrigeration applications.

Mezi klíčové vlastnosti patří:

  • Adjustable differential and range for precise control.
  • Vysoký-amp rated SPST (Single Pole, Single Throw) switch design.
  • Compatible with refrigerants R12, R22, R134A, and R502.
  • Easy-to-read scale plate for setting adjustments.
Ranco O10-1402 Low Pressure Control front view

Obrázek 1: Přední strana view of the Ranco O10-1402 Low Pressure Control, showing the pressure scale and Ranco logo.

Specifikace

AtributHodnota
PoložkaOvládání jedním tlakem
TypNízký tlak
Typ přepínačeSPST
Přepnout akciOpens On Low Pressure
Rozsah tlaku (PSI)(12") to 50 (0.4 to 3.5 bar)
Differential Pressure (PSI)5 to 35 (0.3 to 2.4 bar)
ResetovatAuto
Tlakové připojení36" Capillary with 1/4" Flare Nut
Capillary Length (In.)36
MontážUniversal / Panel Mount
PřílohaNEMA 1
Provozní režimAutomatický
Typ kontaktuNormálně zavřeno
Kontaktní materiálKov
Rozměry produktu9 x 7 x 5 palce

Nastavení a instalace

Proper installation is crucial for the safe and effective operation of the Ranco O10-1402. It is recommended that installation be performed by a qualified technician.

Montáž

The control features universal mounting capabilities. Ensure the mounting surface is stable and free from excessive vibration. Use appropriate fasteners for secure attachment.

Ranco O10-1402 Low Pressure Control with mounting bracket and accessories

Figure 2: Ranco O10-1402 Low Pressure Control shown with its mounting bracket and installation accessories, including screws and instructions.

Tlakové připojení

  1. Connect the 36-inch copper capillary tube with the 1/4" flare nut to the low-pressure side of the refrigeration system.
  2. Ensure all connections are tight to prevent refrigerant leaks. Use appropriate sealing compounds if necessary.
Zadní view of Ranco O10-1402 Low Pressure Control showing capillary tube connection

Obrázek 3: Zadní view of the Ranco O10-1402, highlighting the capillary tube connection point.

Elektrické rozvody

The control features an SPST switch. Refer to the wiring diagram provided with your specific system or consult a qualified electrician for proper electrical connections. Ensure power is disconnected before wiring.

Vnitřní view of Ranco O10-1402 Low Pressure Control showing electrical terminals

Obrázek 4: Vnitřní view of the Ranco O10-1402 with the cover removed, showing the electrical terminals and adjustment mechanism.

Návod k obsluze

Setting Pressure Range and Differential

The Ranco O10-1402 allows for adjustment of both the pressure range and differential. These settings determine the cut-in and cut-out points of the compressor.

  1. Úprava rozsahu: Use a screwdriver to adjust the main pressure setting. The scale plate indicates the pressure at which the switch will open (cut-out).
  2. Nastavení diferenciálu: Adjust the differential setting to determine the pressure difference between the cut-out and cut-in points. The cut-in pressure will be the cut-out pressure plus the differential.
  3. Refer to your system's specifications for recommended pressure and differential settings.
Close-up of Ranco O10-1402 Low Pressure Control showing pressure scale and adjustment screw

Obrázek 5: Detail view of the Ranco O10-1402's front panel, detailing the pressure scale and the adjustment screw for setting the control parameters.

The control is designed for automatic reset, meaning it will automatically close (cut-in) once the pressure rises above the set cut-out pressure plus the differential.

Údržba

The Ranco O10-1402 Low Pressure Control is designed for reliable operation with minimal maintenance. However, periodic checks are recommended to ensure continued performance.

  • Vizuální kontrola: Regularly inspect the control for any signs of physical damage, corrosion, or loose connections.
  • Kapilární trubice: Check the capillary tube for kinks, damage, or leaks. Ensure it is securely fastened and not exposed to excessive heat or sharp objects.
  • Elektrické připojení: Zkontrolujte, zda jsou všechna elektrická připojení bezpečná a bez koroze.
  • Čištění: Keep the exterior of the control clean and free from dust and debris. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.

Poznámka: Any internal repairs or adjustments beyond the specified range and differential settings should only be performed by qualified service personnel.

Odstraňování problémů

Tato část obsahuje pokyny pro řešení běžných problémů. V případě složitých problémů se obraťte na kvalifikovaného technika.

ProblémMožná příčinaŘešení
Compressor not cyclingIncorrect pressure setting; Faulty wiring; Low refrigerant charge.Verify pressure and differential settings; Check electrical connections; Inspect refrigerant levels.
Control not responding to pressure changesDamaged capillary tube; Internal control failure.Inspect capillary tube for damage or kinks; If tube is intact, control may need replacement.
Nepravidelný provozVibration; Loose connections; Contamination.Ensure secure mounting; Tighten all connections; Clean control exterior.

Záruka a podpora

For warranty information or technical support regarding your Ranco O10-1402 Low Pressure Control, please contact the manufacturer, CAI - RANCO, or your authorized distributor. Keep your purchase receipt and model number (O10-1402) readily available when seeking support.

Manufacturer: CAI - RANCO

Date First Available: September 24, 2018

Související dokumenty - O10-1402

Předview Ranco O10/O11/O16/O20 Single Pressure Control Installation Data
Comprehensive installation data, wiring, settings, and specifications for Ranco O10, O11, O16, and O20 single pressure controls used in commercial refrigeration and air conditioning systems. Includes mounting instructions, capillary care, control wiring, adjustment procedures, and detailed specifications.
Předview Instalační data pro jednotlivá tlaková regulace Ranco
Instalační data pro tlakové regulátory Ranco s jedním regulátorem (010, 011, 016, 020). Zahrnují popis, použití, instalaci, zapojení a nastavení regulace pro různá chladiva a tlakové rozsahy.
Předview Ranco O12/O22 Dual Pressure Controls Installation Data
Installation guide for Ranco O12/O22 dual pressure controls, covering description, application, installation, wiring, and adjustments for commercial refrigeration and air conditioning systems.
Předview Katalog chladicích řídicích jednotek Ranco, Johnson Controls a Danfoss
Komplexní katalog regulátorů teploty a tlaku Ranco, Johnson Controls a Danfoss, včetně regulátorů nízkého tlaku, regulátorů vysokého a nízkého tlaku, elektronických regulátorů, regulátorů odmrazování a příslušenství pro chladicí systémy.
Předview Ranco ETC Two Stage Elektronická regulace teploty - instalační data NEMA typ 4X
Instalační data, specifikace, provoz a řešení problémů pro Ranco ETC Two Stage Elektronická regulace teploty, NEMA typ 4X. Tato regulace je určena pro komerční vytápění, větrání a klimatizaci a chlazení a nabízí dvojítagRegulace teploty, LCD displej, programování pomocí klávesnice a vodotěsné pouzdro NEMA 4X pro venkovní použití.
Předview Ranco ETC Single Stage Electronic Temperature Control Installation Instructions
Comprehensive installation, operation, and troubleshooting guide for the Ranco ETC Single Stage Electronic Temperature Control. Covers product details, applications, features, specifications, ordering, programming, lockout switch, wiring diagrams, and sensor information for HVAC and refrigeration systems.