Danfoss 067L5955

Danfoss TR6 TXV Thermostatic Expansion Valve Kit

Model: 067L5955

For 1.5 to 3 ton Traditional HVAC Systems - A/C, Heat Pump, Bi Flow

1. Konec produktuview

The Danfoss TR6 thermostatic expansion valve is engineered for precise control of refrigerant flow in ducted split (residential) and light commercial air conditioning systems. Its hermetically sealed design and robust construction ensure long-term reliability and performance.

Danfoss TR6 TXV Thermostatic Expansion Valve Kit

Figure 1: The Danfoss TR6 TXV Thermostatic Expansion Valve Kit, showing its brass body, capillary tube, and sensing bulb.

Klíčové vlastnosti:

Internal components of Danfoss TR6 TXV

Obrázek 2: Průřez view of the Danfoss TR6 TXV, highlighting internal components such as the hermetic power head, anti-hunt charge, robust stainless steel capillary tube, and built-in check valve.

2. Instalace a nastavení

The Danfoss TR6 kit includes all necessary components for installation. Professional installation by a qualified HVAC technician is recommended to ensure proper function and system integrity.

Zahrnuté komponenty:

Obecné pokyny pro instalaci:

  1. Příprava systému: Ensure the HVAC system is depressurized and isolated before beginning installation.
  2. Spojení: Connect the valve to the evaporator using the appropriate fittings (aeroquip, chatleff, or flare) provided in the kit. Bimetal connections allow for soldering without excessive heat transfer.
  3. Bulb Placement: Securely attach the sensing bulb to the suction line using the provided bulb strap and insulating tape. Proper bulb placement is critical for accurate superheat control.
  4. Equalization Line: Connect the external equalization line (if applicable) to the suction line.
  5. Kontrola těsnosti: After installation, perform a thorough leak check on all connections.
  6. System Evacuation and Charging: Evacuate the system to remove non-condensables and moisture, then charge with the correct refrigerant (R410A).
  7. Nastavení přehřátí: The valve features adjustable superheat. Adjustments should be made by a qualified technician according to system requirements.
Danfoss TR6 TXV dimensions

Figure 3: Technical drawing illustrating the dimensions of the Danfoss TR6 TXV in millimeters and inches.

System Integration Diagrams:

Traditional air conditioning system diagram

Figure 4: Diagram of a traditional air conditioning system (cooling only) showing the placement of the TR6 valve (A) controlling liquid injection in one direction.

Traditional air conditioning heat pump system diagram

Figure 5: Diagram of a traditional air conditioning / heat pump system with two TR6 valves (C and G), illustrating their function in cooling and heating modes with built-in check valves.

Simplified bi-flow air conditioning heat pump system diagram

Figure 6: Diagram of a simplified air conditioning / heat pump system (bi-flow) using a single TR6 valve (C) without an internal check valve, controlling liquid injection in both directions.

Danfoss TR6 TXV detailed dimensions

Figure 7: Detailed technical drawing of the Danfoss TR6 TXV, showing various dimensions and connection points.

Izometrické view of Danfoss TR6 TXV

Figure 8: Isometric view of the Danfoss TR6 TXV, providing a three-dimensional perspective of the valve and its components.

3. Principy fungování

The Danfoss TR6 thermostatic expansion valve regulates the flow of liquid refrigerant into the evaporator based on the superheat of the refrigerant vapor leaving the evaporator. The sensing bulb, attached to the suction line, monitors the refrigerant temperature. Changes in this temperature cause the charge within the bulb to expand or contract, which in turn opens or closes the valve orifice, maintaining optimal superheat and ensuring efficient system operation.

The balanced port design minimizes the influence of varying condensing pressures on the valve's operation, providing stable control. For heat pump applications, the built-in check valve allows refrigerant flow in one direction while preventing it in the opposite, ensuring proper operation during heating and cooling cycles.

4. Údržba

The Danfoss TR6 TXV is designed for long-term, maintenance-free operation due to its robust and hermetically sealed construction. Regular maintenance of the overall HVAC system, including filter changes and coil cleaning, will contribute to the longevity and efficiency of the expansion valve.

5. Řešení problémů

Troubleshooting issues related to the expansion valve typically involves diagnosing refrigerant flow problems or incorrect superheat. Always consult a qualified HVAC technician for diagnosis and repair.

Časté příznaky a možné příčiny:

For complex issues, it is recommended to use diagnostic tools such as pressure gauges and temperature probes to accurately assess system performance and identify the root cause.

6. Specifikace

SpecifikaceHodnota
ZnačkaDanfoss
Číslo modelu067L5955
MateriálNerezová ocel, mosaz
Rozměry položky (D x Š x V)2.75 x 3.5 x 2.5 palce
Hmotnost položky1.45 libry (0.53 kg)
Velikost vstupního připojení3/8 palce
Typ vstupního připojeníOutside Diameter Flared (ODF)
Velikost výstupního připojení3/8 palce
Typ výstupního připojeníSvětlice
Maximální provozní tlak49 baru
Počet portů2
Orifice Capacity3 TR (10.50 kW)
Kompatibilní chladivaR410A
Tovární nastavení10.22 bar / 133.5 psig
Temperature Range (MIN)-10 degC / 15 degF
Temperature Range (MAX)15 degC / 60 degF
NastavitelnýAno
Zpětný ventilAno (vestavěný)
Délka kapilární trubice800 mm / 31.5 palce

7. Záruka a podpora

Warranty information for the Danfoss TR6 TXV Thermostatic Expansion Valve Kit is typically provided by the manufacturer, Danfoss, or the authorized seller at the time of purchase. Please refer to your purchase documentation or contact the seller for specific warranty terms and conditions.

For technical support, installation assistance, or further product information, please contact Danfoss directly or consult their official website. Danfoss also offers the Coolselector®2 app, an advanced calculation and selection software, which can assist in selecting appropriate Danfoss components for your HVAC system.

Související dokumenty - 067L5955

Předview Danfoss Universal TR 6 TXV: Energetická účinnost a náhrada od výrobce pro systémy HVAC
Prozkoumejte termostatický expanzní ventil (TXV) Danfoss Universal TR 6 pro klimatizaci a tepelná čerpadla v domácnostech. Mezi jeho vlastnosti patří významná zvýšení energetické účinnosti, možnosti výměny od výrobců originálních dílů (OEM) a podrobné technické specifikace pro systémy s R-22 a R-410A.
Předview Návod k instalaci termostatického expanzního ventilu Danfoss TR6
Instalační návod pro termostatický expanzní ventil Danfoss TR6, zahrnující chladiva, pracovní tlak, směr proudění, nastavení a technické specifikace.
Předview Návod k instalaci termostatického expanzního ventilu Danfoss TR6
Instalační návod pro termostatický expanzní ventil Danfoss TR6, který zahrnuje kompatibilitu chladiva, pracovní tlak, směr proudění, nastavení a technické specifikace.
Předview Danfoss TR6 Thermostatic Expansion Valve Technical Data and Application Guide
Comprehensive guide to the Danfoss TR6 thermostatic expansion valve, covering its features, applications in HVAC/R systems, technical specifications, sizing, ordering information, and design principles. Includes diagrams and tables for easy reference.
Předview Danfoss TGE Series Thermostatic Expansion Valves - Technical Data
Comprehensive technical data and specifications for Danfoss TGE series thermostatic expansion valves, including types TGE 10, TGE 20, and TGE 40. Covers applications, features, operating conditions, technical data, sizing, and ordering information for various refrigerants.
Předview Instalační příručka termostatického expanzního ventilu Danfoss TCBE/TCCE/TCAE
This installation guide provides detailed instructions for Danfoss TCBE, TCCE, and TCAE series thermostatic expansion valves. It covers general specifications like maximum working and test pressures, temperature limits, connection sizes, and essential installation steps including pressure testing and superheat adjustment. The guide also includes a table for superheat settings based on different refrigerants (R22/R407C, R134a, R404A/R507, R410A) and operating temperature ranges (N, NM, B).