Simplex S4099-9006

Simplex 4099-9006 Double Action, Push Pull Down Fire Alarm Station

Model: S4099-9006

1. Úvod

This manual provides comprehensive instructions for the installation, operation, and maintenance of the Simplex 4099-9006 Double Action, Push Pull Down Fire Alarm Station. This device is designed to initiate a fire alarm signal when manually activated, contributing to the overall safety and security of a building's occupants.

The Simplex 4099-9006 is an IDNet addressable manual pull station with an integrated LED indicator, ensuring reliable communication within compatible fire alarm systems.

2. Bezpečnostní informace

WARNING: Installation and servicing of this device must be performed by qualified personnel only, in accordance with all local and national electrical codes, and the National Fire Alarm and Signaling Code (NFPA 72).

  • Always disconnect power to the fire alarm control panel before installing or servicing the pull station.
  • Zajistěte správné uzemnění, abyste zabránili úrazu elektrickým proudem.
  • Do not paint over the pull station or obstruct its operation.
  • Test the pull station regularly as part of a comprehensive fire alarm system testing schedule.
  • Toto zařízení není určeno pro venkovní použití, pokud není pro takové prostředí výslovně dimenzováno.

3. Konec produktuview

The Simplex 4099-9006 is a robust, red-colored manual fire alarm pull station featuring a double-action mechanism (push then pull). It includes an integrated LED indicator for status feedback.

Simplex 4099-9006 Double Action Fire Alarm Pull Station with installation instructions

Figure 3.1: Simplex 4099-9006 Double Action Fire Alarm Pull Station. This image displays the front of the red pull station with "FIRE ALARM" and "PUSH PULL DOWN" labels, alongside a detailed instruction sheet for installation and mounting, and a small bag of mounting hardware.

Mezi klíčové komponenty patří:

  • Activation Handle: The "PUSH PULL DOWN" mechanism used to initiate an alarm.
  • LED indikátor: Provides visual status of the device (e.g., normal, alarm, trouble).
  • Svorkovnice: For connecting to the fire alarm control panel's IDNet circuit.
  • Mounting Plate/Housing: Secures the device to a standard electrical box or surface.

4. Nastavení a instalace

The Simplex 4099-9006 pull station can be installed using either single-gang or two-part mounting methods, typically on a standard 4-inch square electrical box (not supplied).

4.1 Kontroly před instalací

  • Verify that the fire alarm control panel is powered off.
  • Ensure the mounting location is clean, dry, and meets local code requirements for height and accessibility.
  • Confirm all necessary tools and hardware are available (e.g., screwdriver, wire strippers, mounting screws).

4.2 Mounting Procedures

Refer to the installation diagrams provided with the product and shown in Figure 3.1 for visual guidance.

4.2.1 Single-Gang Mounting

  1. Secure the pull station directly to a standard single-gang electrical box.
  2. Ensure the device is flush with the wall surface.

4.2.2 Two-Part Mounting

  1. Install the backbox or mounting plate first, typically a 4-inch square electrical box.
  2. Mount the pull station assembly onto the installed backbox.
  3. This method may be used for flush trim or surface mounting applications.

4.3 Zapojení

The 4099-9006 is an IDNet addressable device. Connect the pull station to the IDNet circuit of the fire alarm control panel using appropriate gauge wiring, following the wiring diagram provided on the device or in its specific installation sheet. Ensure polarity is correct.

  • Connect the incoming and outgoing IDNet circuit wires to the designated terminals.
  • Ujistěte se, že všechna připojení jsou bezpečná a bez zkratů.

4.4 Po instalaci

  • Once installed and wired, restore power to the fire alarm control panel.
  • Verify the LED indicator on the pull station shows a normal operating status (typically a slow flash).
  • Perform a functional test of the pull station as described in the "Operating Instructions" section.

5. Návod k obsluze

The Simplex 4099-9006 features a double-action activation mechanism to prevent accidental alarms.

5.1 Aktivace alarmu

  1. TAM: Firmly push the "PUSH" bar located at the top of the activation handle.
  2. STRHNOUT: Once the "PUSH" bar is depressed, pull the handle "PULL DOWN" until it latches in the alarm position.
  3. Upon activation, the pull station will send an alarm signal to the fire alarm control panel, and the integrated LED will illuminate steadily (or change to a rapid flash, depending on system programming) to indicate an alarm state.

5.2 Resetting the Pull Station

To reset the pull station after an alarm, a special key (not included with this specific model, as indicated by "No Key" in the product title, implying a different reset mechanism or system-level reset) or tool is typically required to return the handle to its normal, non-alarm position. For the 4099-9006, the reset mechanism is internal and does not require a key. Simply push the handle back into its original position. The fire alarm control panel must also be reset to clear the alarm condition from the system.

6. Údržba

Regular maintenance ensures the reliable operation of your Simplex 4099-9006 pull station. All maintenance should be performed by qualified personnel.

6.1 Pravidelné kontroly

  • Vizuální kontrola (měsíčně): Check for any physical damage, obstructions, or signs of tampering. Ensure the pull station is clean and clearly visible.
  • LED Status (Monthly): Verify the LED indicator is showing a normal operating status (e.g., slow flash).

6.2 Functional Testing (Annually or as per local codes)

Functional testing should be conducted by a certified fire alarm technician.

  1. Notify building occupants and the monitoring station before testing.
  2. Activate the pull station as described in "Operating Instructions".
  3. Verify that the fire alarm control panel receives the alarm signal and initiates appropriate responses (e.g., sounding alarms, notifying monitoring station).
  4. Reset the pull station and the fire alarm control panel.
  5. Confirm the pull station returns to a normal operating state.

6.3 Čištění

Vnější povrch tažné stanice očistěte měkkým,amp hadříkem. Nepoužívejte abrazivní čisticí prostředky ani rozpouštědla, protože by mohly poškodit povrchovou úpravu nebo vnitřní součásti.

7. Řešení problémů

Tato část se zabývá běžnými problémy, se kterými se můžete setkat u požární stanice Simplex 4099-9006. V případě složitějších problémů se obraťte na kvalifikovaného technika požárního hlásiče.

ProblémMožná příčinaŘešení
Pull Station does not activate alarm.Incorrect activation procedure; wiring issue; device fault; control panel issue.Ensure proper push-then-pull action. Check wiring connections. Verify control panel status. Contact technician if problem persists.
LED indicator is off or shows trouble.No power; wiring fault; device fault; control panel trouble.Check power to the control panel. Inspect wiring for breaks or shorts. Consult control panel manual for trouble codes. Contact technician.
Falešný poplach.Accidental activation; faulty device; wiring issue.Reset the pull station and control panel. Inspect for physical damage or obstructions. If recurring, contact technician.
Pull station handle does not reset.Problém s vnitřním mechanismem; nečistoty.Ensure no debris is obstructing the mechanism. Gently attempt to push the handle back. If it remains stuck, the unit may need replacement.

8. Specifikace

FunkceDetail
Číslo modeluS4099-9006
Typ produktuDouble Action Manual Fire Alarm Pull Station
ZnačkaSimplexní
VýrobceSIMPLEX Grinnell
BarvaČervený
Způsob aktivacePush then Pull Down
Key Requirement for ResetNo Key Required (Internal Reset)
KonektivitaIDNet Addressable
Integrované funkceLED indikátor
Hmotnost položky0.5 libry (přibližně 8 uncí)
Rozměry produktu6 x 6 x 4 palce (přibližně)
UPC643485653004
Datum první dostupnosti21. prosince 2015
Simplex 4099-9006 product packaging boxSimplex 4099-9006 product packaging box with PID and Part No.

Figure 8.1: Product packaging for the Simplex 4099-9006, showing the brown cardboard box with product identification labels. The labels confirm PID 4099-9006 and Part No. 06501211.

9. Záruka a podpora

9.1 Informace o záruce

This Simplex product is typically covered by a manufacturer's warranty against defects in materials and workmanship. Specific warranty terms and duration may vary. Please refer to the original purchase documentation or contact Simplex customer service for detailed warranty information.

Note: The product listing mentions "12 months warranty" and "30 days return if not satisfied". This information is from a third-party seller and may not reflect the official manufacturer's warranty. Always verify with the manufacturer.

9.2 Technická podpora

For technical assistance, installation guidance, or troubleshooting beyond the scope of this manual, please contact a certified fire alarm technician or the manufacturer directly.

Simplex Customer Support: Please visit the official SimplexGrinnell webkontaktní údaje naleznete na webu nebo na obalu produktu.

S obecnými dotazy se můžete také obrátit na Simplex brand page on Amazon.

Související dokumenty - S4099-9006

Předview Adresovatelné manuální požární hlásiče Simplex IDNet/MAPNET II – Produktová data
Podrobné informace o adresovatelných manuálních požárních hlásičích Simplex řady 4099, kompatibilních se systémy IDNet a MAPNET II. Vlastnosti, specifikace, možnosti montáže a výběr produktů pro různé modely, včetně jednočinných, dvojčinných (rozbití skla a stisknutí) a variant NO GRIP. V souladu s požadavky ADA a s certifikací UL, ULC, FM a CSFM.
Předview Simplexní adresovatelné manuální stanice: Periferie IDNet/MAPNET II
Prozkoumejte adresovatelné manuální požární hlásiče Simplex s podrobným popisem jejich funkcí, typů s jednou/dvojitou akcí, možností BEZ ÚCHOPU a kompatibility se systémy IDNet/MAPNET II. Zahrnuje informace o montáži a specifikaci.
Předview Datový list pro ruční požární hlásiče Simplex řady 2099 s jednou a dvěma akcemi
Datový list pro nekódované, neadresovatelné ruční požární hlásiče řady Simplex 2099. Zahrnuje funkce, typy ovládání, aplikační reference, výběr produktů, možnosti montáže a specifikace.
Předview Simplex 4010ES: Systèmes de commande d'extinction automatique pour gicleurs
Technika vedení Simplex 4010ES podrobné moduly příkazů pro automatické zániky systémů par gicleurs, couvrant les modes déluge et préventif, as specifikacemi, homologacemi a schématy de câblage.
Předview Simplex 4099-9801C IDNet™ 2-Stage Station IAM Installation Instructions
Installation instructions for the Simplex 4099-9801C IDNet™ 2-Stage Station Individual Addressable Module (IAM). Covers mechanical installation, electrical connections, and address configuration for fire alarm systems.
Předview Ústředna požárního poplachu Simplex 4004: Pokyny k instalaci a provozu
Komplexní průvodce instalací, provozem a programováním ústředny požárního poplachu Simplex 4004 (FACP), včetně systémovéhoview, požadavky, zapojení, popisy modulů a řešení problémů.