The Mastercool 52246 Compact Subcool/Superheat Calculator is a versatile instrument designed for HVAC/R technicians. It combines a temperature gauge and a pressure-to-temperature chart into a single, easy-to-use device. This calculator simplifies the process of determining subcool and superheat temperatures, eliminating the need for manual chart lookups and complex calculations.
This manual will guide you through the proper use and care of your calculator to ensure accurate and reliable measurements.
Co je v krabici
- Mastercool 52246 Compact Subcool/Superheat Calculator
- Clamp-on K-Type Thermocouple
- Battery (typically 9V Duracell, pre-installed or included)

Figure 1: Mastercool 52246 Calculator and included K-Type thermocouple.
Nastavení
- Instalace baterie: Ensure a 9V battery is correctly installed in the battery compartment located on the back of the unit.
- Connect Thermocouple: Plug the yellow K-Type thermocouple connector into the corresponding port on the side of the calculator.
- Zapnutí: Stiskněte tlačítko napájení (U) pro zapnutí zařízení.

Figure 2: Connecting the K-Type thermocouple to the calculator.
Návod k obsluze
The Mastercool 52246 calculator simplifies subcool and superheat measurements into three main steps:
- Select Refrigerant:
- Po zapnutí použijte UP a DOLŮ arrow buttons to scroll through the list of 37 pre-programmed refrigerants (e.g., R22, R32, R134a, R410A).
- Stiskněte tlačítko ENTER button to confirm your selection. The device will remember the last refrigerant used for convenience.
- Enter Pressure:
- Read the pressure from your manifold gauges.
- Použijte UP a DOLŮ arrow buttons on the calculator to adjust the displayed pressure to match your gauge reading. The calculator supports pressure displays in Kg/cm², MPa, Bar, and PSI (0-600 PSI).
- Clamp Termočlánek:
- Bezpečně třamp the K-Type thermocouple onto the appropriate refrigerant line (e.g., suction line for superheat, liquid line for subcool).
- The actual temperature will be displayed in the upper right corner of the LCD.
The calculator will instantly display the calculated subcool or superheat temperature based on your inputs.
Další funkce:
- Toggle Subcool/Superheat: Stiskněte tlačítko SH/SC button to switch between displaying subcool and superheat values.
- Funkce Hold: Stiskněte tlačítko DRŽET button to freeze the current readings on the display. This allows you to record the values even if the thermocouple is disconnected or the unit is turned off. The held data will remain until the instrument is powered off.
- Výběr jednotky: Stiskněte tlačítko JEDNOTKY button to cycle through temperature units (°F or °C) and pressure units (Kg/cm², MPa, Bar, PSI).
Video 1: Demonstration of the Mastercool Compact Subcool/Superheat Calculator in use. This video shows the step-by-step process of selecting refrigerants, entering pressure, and clamping the thermocouple to obtain readings.
Údržba
- Čištění: Jednotku otřete měkkým, damp tkanina. Nepoužívejte abrazivní čisticí prostředky nebo rozpouštědla.
- Výměna baterie: Replace the 9V battery when the low battery indicator appears on the display. Ensure proper polarity during installation.
- Péče o termočlánky: Handle the clamp-on thermocouple with care. Avoid bending or kinking the wire excessively. Clean the clamp jaws regularly to ensure good contact.
- Skladování: Store the calculator in a dry, cool place away from direct sunlight and extreme temperatures.
Odstraňování problémů
| Problém | Možná příčina | Řešení |
|---|---|---|
| Displej je prázdný nebo tmavý | Slabá nebo vybitá baterie; Nesprávná instalace baterie | Vyměňte 9V baterii; Ujistěte se, že je baterie vložena se správnou polaritou. |
| Nepřesné údaje o teplotě | Thermocouple not properly connected or damaged; Poor contact with refrigerant line; Incorrect refrigerant selected | Ensure thermocouple is securely plugged in; Check thermocouple for visible damage; Ensure clamp makes good contact; Verify the correct refrigerant is selected. |
| Calculator does not respond to button presses | Unit frozen; Low battery | Remove and reinsert battery to reset; Replace battery. |
Specifikace
- Model: 52246
- Chladiva: 37 pre-programmed (R22, R32, R114, R123, R124, R134, R134a, R141B, R142B, R290, R401A, R401B, R404A, R407A, R407B, R407C, R407D, R407F, R408A, R409A, R410A, R411A, R411B, R414A, R414B, R417A, R421A, R422A, R422B, R422C, R422D, R427A, R434A, R437A, R438A, R441A, R507A)
- Jednotky teploty: ° F nebo ° C
- Jednotky tlaku: Kg/cm², MPa, Bar, PSI (0-600 PSI)
- Zobrazit: Bubble, Saturated, and Dew Point Temperatures
- Zahrnuté příslušenství: Clamp-on K-Type thermocouple
- Zdroj napájení: Napájení z baterie
- Hmotnost položky: 0.32 unce
- Rozměry produktu: 7.6 x 4 x 2.2 palce

Figure 3: Dimensions of the Mastercool 52246 Calculator.
Informace o záruce
Mastercool products are manufactured to high-quality standards. This product is covered by a limited warranty against defects in materials and workmanship. For specific warranty terms and conditions, please refer to the warranty card included with your product or visit the official Mastercool webmísto.
Zákaznická podpora
For technical assistance, troubleshooting, or warranty inquiries, please contact Mastercool customer support:
- Webmísto: www.mastercool.com