Zurn 1-950XLT2

Uživatelská příručka k dvojitému zpětnému ventilu Wilkins Zurn 1-950XLT2

Model: 1-950XLT2 | Brand: Zurn

Zavedení

This manual provides essential information for the proper installation, operation, and maintenance of the Zurn 1-950XLT2 Wilkins Double Check Valve Backflow Preventer. This device is designed to protect potable water supplies from contamination or pollution due to back-siphonage or backpressure from non-potable sources. Adherence to these instructions is crucial for optimal performance and compliance with local regulations.

The Zurn 1-950XLT2 is suitable for a wide range of applications, including residential, commercial, industrial, irrigation, marine, and fire protection systems. It features a bronze body construction, Noryl replaceable seats, and silicone rubber check discs, ensuring durability and reliable operation.

Bezpečnostní informace

  • Před jakoukoli instalací, údržbou nebo opravou vždy systém odtlakujte.
  • Používejte vhodné osobní ochranné prostředky (OOP), včetně ochranných brýlí a rukavic.
  • Ensure all local plumbing codes and regulations are followed during installation and testing.
  • Only qualified personnel should install and service this backflow preventer.
  • Do not use this device for applications exceeding its specified temperature and pressure ratings.

Konec produktuview

The Zurn 1-950XLT2 is a double check valve assembly designed to prevent backflow. It consists of two independently operating, spring-loaded check valves, two full port shut-off valves, and four ball valve test cocks for field testing.

Zurn 1-950XLT2 Wilkins Double Check Valve Backflow Preventer, front view

Obrázek 1: Přední view of the Zurn 1-950XLT2 Double Check Valve Backflow Preventer. This image shows the bronze body, the two main check valve sections, and the green-handled shut-off valves on either end. The model number and pressure rating are visible on the body.

Zurn 1-950XLT2 Wilkins Double Check Valve Backflow Preventer, angled view

Obrázek 2: Úhlové view of the Zurn 1-950XLT2, highlighting the full port connections and the overall compact design. The green handles of the shut-off valves are clearly visible.

Zurn 1-950XLT2 Wilkins Double Check Valve Backflow Preventer, top view with test cocks

Obrázek 3: Nahoru view of the Zurn 1-950XLT2, showing the four black-capped ball valve test cocks positioned along the body, essential for testing the check valves.

Instalace

Kontroly před instalací

  • Verify that the model number and size match the system requirements.
  • Inspect the unit for any signs of damage from shipping.
  • Ujistěte se, že jsou k dispozici všechny potřebné nástroje a materiály.
  • Confirm compliance with local plumbing codes for backflow prevention devices.

Montáž a orientace

The Zurn 1-950XLT2 must be installed in a horizontal position with the test cocks facing upwards to allow for proper testing and drainage. Ensure adequate clearance around the unit for maintenance and testing.

Připojení potrubí

  1. Flush the supply line thoroughly to remove any debris before connecting the backflow preventer.
  2. Install the unit with the flow arrow on the body pointing in the direction of water flow.
  3. Use appropriate pipe thread sealant on all threaded connections. Avoid overtightening.
  4. Ensure the shut-off valves are in the closed position during installation.
  5. Gradually open the upstream shut-off valve to slowly fill the device and system, allowing air to escape through the test cocks.
  6. Once filled, slowly open the downstream shut-off valve.

Operace

The Zurn 1-950XLT2 operates automatically to prevent backflow. Under normal flow conditions, both check valves are open. If a backpressure or back-siphonage condition occurs, the check valves close to prevent reverse flow.

Uzavírací ventily

The unit is equipped with two full port shut-off valves, one upstream and one downstream. These valves allow for isolation of the backflow preventer for maintenance or testing without shutting down the entire water supply.

  • To close: Turn the green handle 90 degrees until it is perpendicular to the pipe.
  • To open: Turn the green handle 90 degrees until it is parallel to the pipe.

Údržba

Regular maintenance and testing are essential to ensure the continued proper functioning of the backflow preventer and compliance with local regulations.

Annual Testing

The Zurn 1-950XLT2 must be tested annually by a certified backflow prevention device tester. The four ball valve test cocks are provided for this purpose. Refer to local codes for specific testing requirements and frequencies.

Servis

The entire unit is designed to be serviceable in-line. This includes the Noryl replaceable seats and silicone rubber check discs. If repairs are needed, use only genuine Zurn replacement parts.

  1. Isolate the unit by closing both upstream and downstream shut-off valves.
  2. Depressurize the unit by opening the test cocks.
  3. Follow the specific service instructions provided in the detailed service manual (available from Zurn) for disassembling and reassembling the check valve modules.
  4. After servicing, close test cocks, slowly open shut-off valves, and re-test the unit.

Odstraňování problémů

ProblémMožná příčinaŘešení
Water leakage from test cocksTest cock not fully closed; debris in test cock; faulty test cock.Ensure test cock is fully closed. Flush test cock. Replace test cock if damaged.
Continuous discharge from relief valve (if applicable, though this is a DCVA)Not applicable for Double Check Valve Assembly (DCVA). This symptom is typical for a Reduced Pressure Zone (RPZ) assembly.N/A (DCVA does not have a relief valve).
Failure during annual testWorn check valve seats or discs; debris lodged in check valves; damaged springs.Isolate unit, disassemble, inspect, clean, and replace worn components (seats, discs, springs). Re-test after service.
Reduced flow or pressure dropPartially closed shut-off valves; debris accumulation within the unit or upstream piping.Ensure shut-off valves are fully open. Isolate and flush the system. Inspect check valves for debris.

For issues not listed here, or if troubleshooting steps do not resolve the problem, contact a certified plumbing professional or Zurn technical support.

Specifikace

  • Model: Zurn 1-950XLT2 Wilkins Double Check Valve Backflow Preventer
  • Materiál: Bronz
  • Inlet/Outlet Connection Size: 1 palců
  • Typ připojení: Plný přístav
  • Počet portů: 2 (for main flow)
  • Testovací kohouti: 4 Ball Valve Test Cocks
  • Rozsah teplot: 33 °F až 180 °F (0.5 °C až 82 °C)
  • Vnější úprava: Rubber, Silicone (for seals and discs)
  • Rozměry (D x Š x V): Přibližně 10 x 7.5 x 4.5 palce
  • Hmotnost položky: Přibližně 8.1 libry
  • certifikace: NSF/ANSI 372 (Lead Free), NSF/ANSI 61, ASTM B122, ASTM B153, ASSE 1013, ASSE 1014
  • Lead Free Compliance: Ano
Diagram showing Retrofit, Lead Free, and Water Saving icons

Obrázek 4: Informational graphic illustrating key features: "Retrofit" (suitable for retrofit applications), "Lead Free" (low lead compliant), and "Water Saving" (implied benefit of proper backflow prevention). This highlights the product's modern design and compliance.

Záruka a podpora

Informace o záruce

Zurn products are manufactured to high-quality standards. For specific warranty details, please refer to the official Zurn warranty statement included with your product or visit the Zurn webmísto. Uschovejte si doklad o koupi pro případ záručních reklamací.

Zákaznická podpora

For technical assistance, replacement parts, or further information, please contact Zurn customer support. You can find contact details on the official Zurn webna webu nebo prostřednictvím místního distributora.

Zurn Webmísto: www.zurn.com

Související dokumenty - 1-950XLT2

Předview ZURN P1000AXL, TP1100A, TP220, TP3000 Temperature & Pressure Relief Valves - Specifications and Installation
Detailed specifications, materials, dimensions, and installation guidelines for ZURN Wilkins P1000AXL, TP1100A, TP220, and TP3000 Temperature & Pressure Relief Valves designed for water heating storage vessels.
Předview Redukční ventil Zurn Wilkins ZW209FP: Instalace, provoz a údržba
Komplexní průvodce sestavou protipožárního redukčního ventilu Zurn Wilkins ZW209FP, který zahrnuje instalaci, uvedení do provozu, provoz, charakteristiky průtoku a postupy údržby. Obsahuje podrobné pokyny pro hlavní ventil a pilotní ventil PV-PRD.
Předview Sestava dvojitého zpětného ventilu ZÜRN model 350AST: Specifikace a použití
Komplexní technické podrobnosti o sestavě dvojitého zpětného ventilu ZÜRN model 350AST, zahrnující jeho použití v systémech pitné vody, materiály, normy, rozměry, hmotnosti, charakteristiky průtoku a pokyny k instalaci.
Předview Specifikace a instalace tlako-vakuového jističe Zurn Wilkins model 720A
Podrobné informace o sestavě tlakového a vakuového jističe Zurn Wilkins model 720A, včetně jejího použití, shody s normami, materiálů, vlastností, rozměrů, hmotností, charakteristik proudění a pokynů k instalaci pro vnitřní i venkovní použití.
Předview Bezolovnatý redukční ventil Zurn NR3XL: Průvodce instalací, údržbou a opravami
Komplexní průvodce pro bezolovnatý redukční ventil Zurn NR3XL, který zahrnuje instalaci, kontrolu, údržbu, opravy a řešení problémů. Zahrnuje specifikace produktu a informace o záruce.
Předview Zurn NR3XL Water Pressure Reducing Valve with Integral By-Pass Check Valve and Strainer
Detailed specifications and installation guide for the Zurn NR3XL, a water pressure reducing valve designed for potable water lines. Features include an integral strainer, by-pass check valve, and low lead cast bronze body. Suitable for residential and commercial applications.