0063010 wattů

Návod k obsluze zpětného ventilu Watts 009M2 se sníženým tlakem (model 0063010)

For Models: 009M2, 009M2-QT

1. Úvod

This manual provides detailed instructions for the installation, operation, and maintenance of the Watts 009M2 Reduced Pressure Zone (RPZ) Backflow Preventer. This device is designed to protect potable water supplies from contamination due to backpressure or backsiphonage from non-potable sources. It is crucial to read and understand all instructions before installation and use to ensure proper function and safety.

The Watts 009M2 RPZ assembly features a compact, modular design for easy maintenance, with a single access cover for in-line repairs. It is suitable for continuous pressure piping applications and cross-connections identified as health hazards.

2. Důležité bezpečnostní informace

3. Konec produktuview a Komponenty

The Watts 009M2 Reduced Pressure Zone Backflow Preventer is constructed with a durable bronze body and features NPT end connections. Key components include:

Watts 009M2 Reduced Pressure Zone Backflow Preventer
Figure 1: Watts 009M2 Reduced Pressure Zone Backflow Preventer. This image shows the bronze body, quarter-turn shutoff valves with green handles, and multiple test cocks on top.

4. Nastavení a instalace

  1. Kontrola před instalací:
    • Verify that the product model (009M2) and size (2 inch) match your requirements.
    • Zkontrolujte jednotku, zda nedošlo k poškození při přepravě.
    • Ensure all necessary tools and materials for installation are available.
  2. Příprava místa:
    • Choose an installation location that allows for easy access for testing and maintenance.
    • Ensure adequate drainage for the relief valve discharge.
    • The device should be installed horizontally, with the relief valve pointing downwards.
  3. Připojení potrubí:
    • Flush the upstream piping thoroughly to remove any debris before connecting the backflow preventer.
    • Connect the inlet and outlet piping to the NPT connections on the device. Use appropriate thread sealant.
    • Avoid overtightening connections to prevent damage to the bronze body.
    • Ensure the flow arrow on the device body matches the direction of water flow.
  4. Relief Valve Drain:
    • Connect a drain line to the relief valve outlet. The drain line must be adequately sized and sloped to allow for free discharge and prevent backpressure on the relief valve.
    • Ensure the drain line terminates in an air gap, preventing any possibility of cross-connection.
  5. Kontrola po instalaci:
    • Slowly open the upstream shutoff valve, then the downstream shutoff valve, to gradually fill the system and prevent water hammer.
    • Zkontrolujte těsnost všech spojů.
    • Perform initial testing by a certified backflow prevention tester to ensure proper operation and compliance with local codes.

5. Návod k obsluze

The Watts 009M2 is designed for continuous pressure operation. Normal operation involves the device being fully open, allowing water to flow through the system while providing backflow protection.

6. Údržba

Regular maintenance is critical for the reliable performance of your backflow preventer. The modular design and single access cover simplify servicing.

7. Řešení problémů

ProblémMožná příčinaŘešení
Water discharge from relief valve (continuous)
  • Fouled first check valve
  • Damaged relief valve seat or disc
  • Excessive backpressure
  • Clean or repair first check valve.
  • Inspect and replace relief valve components.
  • Identify and correct source of backpressure.
Žádný průtok vody nebo snížený průtok
  • Shutoff valves closed
  • Debris obstructing flow
  • Fouled check valves
  • Ujistěte se, že jsou uzavírací ventily zcela otevřené.
  • Isolate and inspect for debris.
  • Clean or repair check valves.
Netěsnosti z přípojek
  • Nesprávně utěsněné závity
  • Damaged gaskets
  • Re-apply thread sealant and tighten connections.
  • Inspect and replace gaskets.

For issues not listed or if troubleshooting steps do not resolve the problem, contact a certified plumbing professional or Watts technical support.

8. Specifikace

Číslo modelu0063010 (009M2)
Backflow Preventer TypeSestava zóny se sníženým tlakem
Materiál tělaBronz
Velikost vstupního/výstupního připojení2 Inches (50 MM)
Inlet/Outlet Connection TypeFemale Threaded NPT
Maximální pracovní tlak175 PSI (12.10 BAR)
Maximální teplota180 °F (82 °C)
Minimální teplota33 °F (0.5 °C)
Typ ochranyBackpressure and Backsiphonage
Rozměry produktu (D x Š x V)22 x 10 x 8 palce
Hmotnost položky27 libry
Lead Free StatusNO (For non-potable use only)

9. Záruka a podpora

Specific warranty information for Watts products is typically provided with the product packaging or available on the official Watts website. Please refer to these resources for the most current warranty terms and conditions.

For technical support, replacement parts, or further assistance, please contact Watts customer service or visit their official website. Ensure you have your product model number (0063010) and serial number (if applicable) ready when contacting support.

Watts Official Webmísto: www.watts.com