1. Konec produktuview
The Watts 007 QT 1/2-inch Double Check Valve Assembly is engineered to prevent the backflow of contaminated water into a potable water supply system. This device is suitable for non-health hazard, continuous pressure applications. Its robust bronze body construction ensures durability and ease of maintenance. The assembly provides protection against both backsiphonage and backpressure backflow, safeguarding water quality.
Mezi klíčové vlastnosti patří:
- Cast Bronze body construction for durability.
- Designed to prevent reverse flow of polluted water.
- Ideal for non-health hazard continuous pressure applications.
- Protection against backsiphonage and backpressure backflow.
- Ease of maintenance with a single cover and top entry design.
- Replaceable seats and seat discs.
- Modular construction and compact design.
- Top-mounted ball valve test cocks.
- Nízká tlaková ztráta.
- No special tools required for servicing.

Image 1.1: Watts 007 QT 1/2-inch Double Check Valve Assembly. This image displays the bronze body construction and overall compact design of the valve assembly.
2. Bezpečnostní informace
VAROVÁNÍ: Improper installation or maintenance of this device can lead to serious injury or property damage. Always adhere to local plumbing codes and regulations.
- Doporučená profesionální instalace: Installation should be performed by a qualified plumber or certified backflow prevention device tester.
- Místní kódy: Always check with local inspection authorities for specific installation requirements and compliance.
- Limity tlaku: Do not exceed the maximum working pressure of 175 psi (12.06 bar). Exceeding this limit can cause device failure and potential hazards.
- Kvalita vody: This device is for non-health hazard applications. For health hazard applications, a different class of backflow preventer may be required.
- Ochrana očí: Always wear appropriate eye protection when installing, maintaining, or testing the device.
- Vypnutí systému: Ensure the water supply is completely shut off and depressurized before beginning any installation or maintenance procedures.
3. Nastavení a instalace
The Watts 007 QT Double Check Valve Assembly is designed for horizontal or vertical installation, depending on local codes and specific model requirements. Ensure proper orientation for optimal performance.
3.1 Kontroly před instalací
- Verify that the product model (007 QT, 1/2-inch) matches your application requirements.
- Zkontrolujte ventil, zda nevykazuje známky poškození při přepravě.
- Ensure all necessary tools and materials are available, including appropriate pipe fittings and sealing compounds.
- Confirm compliance with all local plumbing codes and regulations.
3.2 kroky instalace
- Uzavření přívodu vody: Locate the main water shut-off valve and turn off the water supply to the area where the backflow preventer will be installed. Drain the system to relieve pressure.
- Vyberte umístění: Choose an accessible location for installation that allows for future maintenance and testing. The device should be installed downstream of the main water meter and upstream of any connections that could introduce contaminants.
- Příprava potrubí: Cut and prepare the existing piping to accommodate the 1/2-inch inlet and outlet connections of the valve assembly. Ensure pipe ends are clean and free of burrs.
- Instalace ventilu: Install the Watts 007 QT assembly into the pipeline, ensuring the flow arrow on the valve body points in the direction of water flow. Use appropriate thread sealant on all connections.
- Utáhněte spoje: Securely tighten all connections to prevent leaks, but do not overtighten, which could damage the bronze body or fittings.
- Otevřený vodovod: Slowly open the main water shut-off valve to gradually repressurize the system. Check all connections for leaks.
- Počáteční testování: After installation, the device should be tested by a certified backflow prevention device tester to ensure proper operation and compliance with local regulations.
4. Provoz
The Watts 007 QT Double Check Valve Assembly operates automatically to prevent backflow. It contains two independently operating check valves that close to prevent reverse flow when a backflow condition occurs.
- Under normal flow conditions, both check valves are open, allowing water to pass through freely with minimal pressure drop.
- If the pressure downstream of the device becomes greater than the supply pressure (backpressure), or if the supply pressure drops below atmospheric pressure (backsiphonage), the check valves will close.
- The design ensures that if one check valve fails, the other provides a secondary barrier against backflow.
- The top-mounted ball valve test cocks allow for easy testing of the device's functionality by a certified technician.
5. Údržba
Regular maintenance and testing are crucial to ensure the continued proper function of your Watts 007 QT Double Check Valve Assembly. This device is designed for ease of service.
5.1 Annual Testing
Local regulations typically require annual testing of backflow prevention devices by a certified tester. This ensures the device is operating correctly and providing the required level of protection.
5.2 Servis a opravy
The modular construction and top-entry design facilitate easy servicing. If testing indicates a malfunction, the internal components can be accessed and replaced without removing the entire assembly from the pipeline.
- Demontáž: To access internal components, ensure the water supply is off and the system is depressurized. Remove the single cover.
- Výměna součásti: The seats and seat discs are replaceable. Use genuine Watts replacement parts to ensure compatibility and performance. No special tools are required for servicing, making repairs straightforward.
- Opětovná montáž: Reassemble the device carefully, ensuring all seals are properly seated and the cover is securely fastened.
- Post-Service Testing: After any servicing or repair, the device must be retested by a certified backflow prevention device tester to confirm proper operation.
6. Řešení problémů
This section provides guidance for common issues. For complex problems or issues related to backflow prevention, always consult a certified professional.
6.1 Běžné problémy a řešení
- Leakage from Test Cocks:
- Příčina: Test cock not fully closed or damaged O-ring.
- Řešení: Ensure test cocks are fully closed. If leakage persists, the O-ring or test cock assembly may need replacement.
- Constant Drip/Leak from Valve Body:
- Příčina: Damaged or worn check valve seats/discs, or debris lodged in the check valve.
- Řešení: Shut off water, depressurize, and inspect the internal check valve components. Clean any debris or replace worn seats/discs.
- Reduced Water Flow/Pressure:
- Příčina: Debris accumulation within the valve, or a check valve partially closed.
- Řešení: Isolate the valve, depressurize, and inspect for debris. If a check valve is stuck, it may require cleaning or replacement of components.
- Failure During Annual Test:
- Příčina: Internal component failure, debris, or improper installation.
- Řešení: A certified backflow tester will diagnose the specific issue. Follow their recommendations for repair or replacement.
If you encounter issues not listed here or are unsure about a repair, contact Watts customer support or a qualified plumbing professional.
7. Specifikace
| Číslo modelu | 007 QT (Part # 0062131) |
| Velikost | 1/2 palce |
| Materiál | Bronze, Silicone |
| Vnější povrch | Bronz |
| Velikost vstupního připojení | 0.5 palce |
| Typ vstupního připojení | Sestava dvojitého zpětného ventilu |
| Velikost výstupního připojení | 0.5 palce |
| Typ výstupního připojení | FNPT |
| Maximální provozní tlak | 175 psi (12.06 baru) |
| Počet portů | 2 |
| Hmotnost položky | 3.45 libry |
| Rozměry produktu (D x Š x V) | 1 x 0.39 x 0.39 palce |
| Specifikace splněna | ASSE 1015, AWWA C510, CSA B64.5, IAPMO PS31 |
8. Záruka a podpora
For specific warranty information regarding your Watts 007 QT Double Check Valve Assembly, please refer to the documentation included with your purchase or visit the official Watts webZáruční podmínky se obvykle vztahují na výrobní vady při běžném používání a servisu.
8.1 Zákaznická podpora
If you require technical assistance, have questions about installation, operation, or maintenance, or need to inquire about replacement parts, please contact Watts customer support:
- Watts Official Webmísto: www.watts.com
- Viz obal produktu nebo informace o výkonu (Watts). website for current contact numbers and email addresses.
When contacting support, please have your product model number (007 QT) and any relevant purchase information readily available.