The EARU EAPDX-63AVE-RGB is a compact, multi-function protective device designed to safeguard electrical circuits and appliances from various power anomalies. It integrates over-voltage, pod-voltage, and over-current protection, along with real-time voltage, current, and energy metering. This device features an adjustable self-resetting mechanism and a high-definition digital display for easy monitoring and configuration.

Obrázek 1: Přední strana view of the EARU Multi-Function Protector.
2. Bezpečnostní informace
- Instalaci a údržbu by měli provádět pouze kvalifikovaní elektrikáři.
- Před jakoukoli instalací nebo elektroinstalačními pracemi se ujistěte, že je odpojeno napájení.
- Verify correct wiring connections according to the provided diagram to prevent damage to the device or connected equipment.
- Do not operate the device in environments exceeding its specified operating temperature or humidity ranges.
- The device is designed for single-phase AC 230V systems. Using it with incompatible voltage systems may cause malfunction or damage.
3. Klíčové vlastnosti
- Over-Voltage ochrana: Adjustable from 230V to 300V (Default: 280V).
- Under-Voltage ochrana: Adjustable from 80V to 210V (Default: 160V).
- Nadproudová ochrana: Adjustable from 1A to 63A (Default: 50A).
- Adjustable Reconnect Time: Delay on time from 1s to 600s (Default: 5s).
- Monitorování v reálném čase: Zobrazuje svtage (V), current (A), and energy consumption (kWh).
- Automatické obnovení: Automatically restores power after fault conditions clear.
- High-Definition Digital Display: Clear and precise readings.
- PC Flame-Retardant Material: Zajišťuje bezpečný a spolehlivý provoz.
- 35MM DIN Rail Mounting: Easy installation in standard electrical panels.

Figure 2: Adjustable self-resetting protection features.
4. Technické specifikace
| Parametr | Hodnota |
|---|---|
| Poláci | 1P+N |
| Jmenovitý proud | 1-63A (nastavitelný) |
| Jmenovitý objemtage | AC 230V |
| Jmenovitá frekvence | 50/60 Hz |
| Provozní svtage Dosah | AC 80V-400V (jednofázové) |
| Over-Voltage Ochrana | 230V-300V (nastavitelné) |
| Under-Voltage Ochrana | 80V-210V (nastavitelné) |
| Ochrana proti nadproudu | 1A-63A (Adjustable) |
| Čas opětovného připojení | 1s-600s (Adjustable) |
| Přesnost měření | ±1 % |
| Instalace | 35MM DIN lišta |
| Provozní teplota | -50-55 ℃ |
| Vlhkost | <50 % při 40 °C (bez kondenzace) |
| Třída ochrany | IP20 |
| Osvědčení | CE |
Obrázek 3: Rozměry a parametry produktu.

5. Instalace
5.1 Montáž
The EARU Multi-Function Protector is designed for 35MM DIN rail mounting. Secure the device onto the DIN rail using its integrated clips. Ensure it is firmly attached to prevent movement.

Figure 4: Protector mounted on a DIN rail.
5.2 Schéma zapojení
Connect the device according to the wiring diagram below. Ensure that the input (IN) and output (OUT) terminals are correctly identified and connected to the Neutral (N) and Live (L) lines of your AC power supply. The device uses single-channel wiring with tunnel-type wiring ports for secure connections.

Figure 5: Front panel and connection points.

Figure 6: Wiring Installation Diagram (refer to the diagram for detailed connections).
Kroky zapojení:
- Před zahájením jakýchkoli zapojení vypněte hlavní napájení.
- Connect the incoming Neutral (N) and Live (L) wires to the 'IN' terminals at the top of the protector.
- Connect the outgoing Neutral (N) and Live (L) wires to the 'OUT' terminals at the bottom of the protector, leading to your load.
- Ujistěte se, že všechny spoje jsou těsné a bezpečné.
6. Obsluha a nastavení
The device features a digital display and three buttons for operation: an 'Up' arrow, a 'Down' arrow, and a 'SET' button. The display shows real-time voltage (V), current (A), and energy consumption (kWh).

Figure 7: High-definition digital display and responsive buttons.
6.1 Navigating the Settings Menu
To enter the setting state, press and hold the 'SET' button for more than 3 seconds. Use the 'Up' and 'Down' arrow buttons to navigate through the menu options and adjust values. Press 'SET' again to confirm a selection or move to the next parameter.
Nabídka nastavení obsahuje:
- Pt (Power-on delay time): 1s-600s
- rE (Protection recovery delay): 1s-600s
- OU (Over-voltage protection setting): 230V-300V
- OUr (Over-voltage recovery setting): 225V-295V
- UU (Under-voltage protection setting): 80V-210V
- UUr (Under-voltage recovery setting): 85V-215V
- UtE (Over-under-voltage protection action delay time): 0.1s-10s
- URd (Calibration Voltage Value): -9.9V ~ 9.9V
- oC (Over current protection value): 1-63A
- CtE (Overcurrent protection action time): 0.1s-60s
- Ctt (Overcurrent protection continuous times): 0-20
- CrAd (Current Calibration): -9.9A ~ 9.9A
- PC (Power range setting): 1-999
- CLP (Reset mode): CLP 003 Reset setting, CLP 008 Reset power level, CLP 009 Restore Factory Settings
For a visual guide on adjusting settings, please refer to the demonstration video:
Video 1: Demonstration of setting adjustments on the EARU Multi-Function Protector.
7. Údržba
- Regularly inspect the device for any signs of physical damage or loose connections.
- Udržujte zařízení čisté a bez prachu a vlhkosti. K čištění používejte suchý, měkký hadřík.
- Nepoužívejte abrazivní čisticí prostředky nebo rozpouštědla.
- Zajistěte dostatečné větrání kolem zařízení, aby nedošlo k přehřátí.
8. Řešení problémů
8.1 Běžné problémy
- Žádný displej/Žádné napájení: Check the input power supply and ensure all wiring connections are secure.
- Časté vypínání zařízení: Review tvůj přehnaný hlasitosttage, pod-voltage, and over-current settings. They might be set too sensitively for your load or power conditions. Adjust the protection values and recovery delays as needed.
- Nesprávné čtení: Jestliže svtage or current readings appear inaccurate, consider performing a calibration using the URd (Voltage Calibration) or CrAd (Current Calibration) settings in the menu.
- Device Not Resetting: Check the 'rE' (Protection recovery delay) setting. The device will wait for this duration before attempting to reconnect after a fault.
8.2 svtage Compatibility (120V AC)
While the device has an operating voltage range of AC 80V-400V, its rated voltage is AC 230V, and default protection settings are optimized for 230V systems. If you intend to use this product in a 120V AC system, you would need to manually adjust the under-voltage a over-voltage protection settings to appropriate values for 120V. However, the device's primary design and default configuration are for 230V applications.
9. Uživatelské tipy
- Resetting kWh to 0: To reset the accumulated energy (kWh) reading, navigate to the settings menu (press and hold 'SET' for 3 seconds), find the 'CLP' option, and select 'CLP 008 Reset power level'. Confirm your selection.
- Obnovení továrního nastavení: If you encounter persistent issues or wish to revert all settings to their original defaults, use the 'CLP 009 Restore Factory Settings' option in the menu.
- Optimální nastavení: For best protection, set your over-voltage a pod-zvtage thresholds slightly above and below your nominal line voltage, respectively, allowing for minor fluctuations without unnecessary tripping.
10. Záruka a podpora
For warranty information and technical support, please contact your retailer or the manufacturer directly. Keep your purchase receipt as proof of purchase. Ensure all installation and operation guidelines are followed to maintain warranty validity.