1. Konec produktuview
The Eastron SDM630Modbus V3 is an advanced multi-function three-phase energy monitoring solution. It is designed for measuring and displaying various electrical parameters in 1-phase 2-wire, 3-phase 3-wire, and 3-phase 4-wire systems. This device is equipped with optional outputs such as pulses and RS485 RTU Modbus communication, making it suitable for integration into PV solar systems and other energy management applications.
It features configuration and display buttons for easy navigation through parameters and settings. The unit is housed for DIN rail mounting and offers IP51 protection. It supports direct connection up to 100A and allows for selectable measurement modes using free configuration software for kWh display, including Total kWh (Import + Export), Import kWh, and Net kWh (Export - Import).

Obrázek 1: Přední strana view of the SDM630Modbus V3
2. Klíčové vlastnosti
- Max. 100A Direct Load
- 4 Module (72mm wide) DIN rail mounting
- Bi-directional Measurement
- 2 Pulse outputs + RS485 Modbus communication
- Multi-measurement capabilities: kWh, kvarh, W, Var, VA, PF, Hz, dmd, V, A, etc.
- Compatible with 3P4W, 3P3W, and 1P2W systems
- Provozní teplota: -25 až +55 stupňů Celsia
- Jmenovitý objemtage: 230 V AC
- Accuracy Class: Cl. 1
- Measuring Energy Range: 0-999999.99 kWh
- Typ displeje: LCD
- Komunikační protokol: Modbus RTU
- Pulse Output 1: Configurable
- Pulse Output 2: 400imp/kWh (Passive type)
3. Instalace a nastavení
3.1 Bezpečnostní opatření
- Instalaci by měl provádět pouze kvalifikovaný personál.
- Před instalací nebo údržbou se ujistěte, že je odpojeno veškeré napájení.
- Dodržujte místní elektrické předpisy a předpisy.
- Nepoužívejte zařízení, pokud se jeví poškozené.
3.2 Montáž
The SDM630Modbus V3 is designed for DIN rail mounting. Securely attach the device to a standard 35mm DIN rail within an appropriate enclosure, ensuring adequate ventilation.

Obrázek 2: Strana view illustrating DIN rail mounting
3.3 Schéma zapojení
The meter supports 1-phase 2-wire, 3-phase 3-wire, and 3-phase 4-wire connections. Refer to the diagram below for correct wiring. Ensure all connections are tight and secure.

Figure 3: Wiring Diagram and Dimensions. The diagram shows connections for 1-phase 2-wire, 3-phase 3-wire, and 3-phase 4-wire systems. For 3-phase 4-wire, L1, L2, L3, and N are connected to terminals 1, 4, 7, and 10 respectively, with corresponding load connections on terminals 3, 6, 9, and 12. RS485 A and B are connected to terminals 13 and 14. Pulse outputs are on terminals 15 and 16.
Poznámky k zapojení:
- Příkon: Connect the phase and neutral wires according to the diagram for your specific system (1P2W, 3P3W, or 3P4W). The meter supports direct connection up to 100A.
- RS485 Komunikace: Connect the RS485 A and B lines to terminals 13 and 14 respectively for Modbus RTU communication.
- Pulzní výstupy: Pulse output 1 and 2 are available on terminals 15 and 16. These are passive outputs.
4. Provoz
The SDM630Modbus V3 features an LCD display and several buttons for navigating and configuring the device.
4.1 Displej a tlačítka
The LCD displays various electrical parameters. The buttons (U/I, M, P, E) allow users to cycle through measurements, access menus, and confirm selections.
- Tlačítko U/I: Typically used to cycle through voltage (U) and current (I) readings, or other instantaneous parameters.
- Tlačítko M: Likely serves as a 'Mode' or 'Menu' button to access different measurement screens or configuration settings.
- Tlačítko P: May be used for 'Parameter' selection or 'Pulse' related settings.
- Tlačítko E: Generally functions as an 'Enter' or 'Exit' button to confirm selections or leave a menu.
For detailed navigation and configuration, refer to the official datasheet and configuration software manual available on the Eastron webmísto.
4.2 Režimy měření
The device can measure a wide range of parameters including:
- Active Energy (kWh) - Total, Import, Export, Net
- Reactive Energy (kvarh)
- Aktivní výkon (W)
- Reactive Power (Var)
- Zdánlivý výkon (VA)
- Power Factor (PF)
- Frekvence (Hz)
- svtage (V)
- proud (A)
- Poptávka (dmd)
- A další.
Specific measurement modes and their display can be configured using the provided software.
5. Údržba
The SDM630Modbus V3 is designed for reliable operation with minimal maintenance. However, periodic checks are recommended:
- Čištění: Udržujte zařízení čisté a bez prachu. K čištění používejte měkký, suchý hadřík. Nepoužívejte abrazivní čisticí prostředky ani rozpouštědla.
- Spojení: Periodically inspect all wiring connections to ensure they remain tight and secure. Loose connections can lead to inaccurate readings or device malfunction.
- Prostředí: Abyste předešli poškození, zajistěte, aby provozní prostředí zůstalo v rámci specifikovaného rozsahu teploty a vlhkosti.
6. Řešení problémů
If you encounter issues with your SDM630Modbus V3, consider the following troubleshooting steps:
- Bez displeje/napájení:
- Zkontrolujte hlavní napájení měřiče.
- Verify all power connections are correctly wired and secure.
- Nepřesná čtení:
- Ensure the wiring configuration matches your electrical system (1P2W, 3P3W, 3P4W).
- Check for loose or incorrect wiring connections.
- Verify that the meter's settings (e.g., CT ratio if applicable, though this model is direct connect up to 100A) are correctly configured.
- Communication Issues (RS485 Modbus):
- Check RS485 A and B connections for correct polarity and secure fit.
- Verify the Modbus address, baud rate, parity, and stop bits settings on both the meter and the master device.
- Ensure the communication cable length does not exceed the maximum recommended distance (1000m).
If problems persist, consult the official datasheet or contact Eastron technical support.
7. Specifikace
Detailed technical specifications for the SDM630Modbus V3 are provided below.

Obrázek 4: Podrobné parametry produktu
| Parametr | Hodnota |
|---|---|
| Název značky | Eastron |
| Číslo modelu | SDM630Modbus V3 |
| Rozměry | 100 * 72 * 66 mm |
| Provozní teplota | -25 až +55 stupňů Celsia |
| Výstupní objemtage | 230V |
| Třída přesnosti | Cl. 1 |
| Rozsah měření energie | 0-999999.99 kWh |
| Fáze | Třífázový |
| Max. provozní proud | 100A (Direct Load) |
| Jmenovitý objemtage | 230V |
| Napájení | AC |
| Typ zobrazení | LCD |
| Potřeby pro kutily | Elektrický |
| Typ komunikace | RS485 |
| Komunikační protokol | Modbus RTU |
| Pulzní výstup 1 | Konfigurovatelné |
| Pulzní výstup 2 | 400imp / kWh |
| Typ pulzního výstupu | Pasivní |
Electrical Characteristics (from image)
| Typ měření | Přesnost |
|---|---|
| Moc | 0.5 % maximálního rozsahu |
| Aktivní energie | IEC 62053-21 Třída 1.0 |
| Jalová energie | IEC62053-23 Třída 2 |
| Frekvence | 0.2 % střední frekvence |
| Proud | 0.5 % maximálního rozsahu |
| svtage | 0.5 % maximálního rozsahu |
| Účiník | 1 % z jednoty (0.01) |
Input & Output (from image)
| Parametr | Hodnota |
|---|---|
| Jmenovitý proud (Ib/Iref) | 10A |
| Max Current (Imax.) | 100A |
| Min Current (Imin.) | 0.5A |
| Počáteční proud | 40 mA |
| Jmenovitý objemtage (ne) | 230V L-N / 120V L-N |
| Operační svtage | 80 % ~ 120 % Un |
| Výstup | 2 impulzní výstupy + RS485 Modbus |
Ethernet Communication (from image)
| Parametr | Hodnota |
|---|---|
| Typ autobusu | RS485 (poloduplexní) |
| Komunikační adresa | 1~247 |
| Přenosová vzdálenost | Maximálně 1000 m |
| Přenosová rychlost | 2400 bps ~ 38400 bps |
| Parita | Žádné (výchozí), liché, sudé |
| Stop bitům | 1 |
8. Záruka a podpora
8.1 Informace o záruce
The Eastron SDM630Modbus V3 comes with an 18-month warranty from the date of purchase.
8.2 Technická podpora a zdroje
- datový list: A detailed datasheet for the SDM630Modbus V3 can be downloaded from the official Eastron webmísto: www.eastrongroup.com.
- Modbus Protocol Instruction / Register Map: For specific Modbus protocol instructions and register maps, please contact Eastron directly.
- Obecné dotazy: For any further questions or support, please contact Eastron customer service.

Obrázek 5: Často kladené otázky
9. Uživatelské tipy
- Kompatibilita invertoru: The SDM630Modbus V3 has been reported by users to be compatible with Deye Inverters. Always verify specific model compatibility with your inverter manufacturer or Eastron support if unsure.
- Konfigurační software: Utilize the free configuration software provided by Eastron to customize measurement modes and display settings for optimal performance in your specific application.