EARU EARU-1012

EARU Electric 3-Phase Auto Transfer Switch (ATS) - 440V 63A User Manual

Brand: EARU | Model: EARU-1012

1. Úvod

This manual provides essential information for the safe and efficient installation, operation, and maintenance of your EARU Electric 3-Phase Auto Transfer Switch (ATS) - 440V 63A. Please read this manual thoroughly before installation and operation to ensure proper functionality and to prevent damage or injury.

The ATS is designed to provide uninterrupted power by automatically transferring loads between phases in a three-phase supply system. It features intelligent monitoring and protection against phase failure, over/under voltage, and overcurrent conditions, ensuring the stability and safety of connected equipment.

2. Bezpečnostní informace

VAROVÁNÍ: Nebezpečí úrazu elektrickým proudem. Instalaci a servis by měl provádět pouze kvalifikovaný personál.

  • Always disconnect power before installing or servicing the ATS.
  • Ujistěte se, že veškeré zapojení splňuje místní a národní elektrotechnické předpisy.
  • Ověřte správný objemtagPřed připojením zařízení zkontrolujte elektrické napájení a jmenovitý proud.
  • Nepoužívejte zařízení, pokud se jeví poškozené.
  • Udržujte děti v dostatečné vzdálenosti od elektrických zařízení.

3. Konec produktuview

The EARU Electric 3-Phase ATS is an intelligent device that continuously monitors your three-phase power supply. It automatically switches single-phase loads to a healthy phase in case of a phase failure or imbalance, ensuring continuous operation of critical equipment.

3.1. Obsah balení

  • 1 x EARU Electric 3-Phase Auto Transfer Switch (ATS)

3.2. Přední panel a indikátory

Front panel of EARU Electric 3-Phase ATS with digital display and control buttons

Popis obrázku: The front panel of the ATS features a digital display showing voltage for L1, L2, L3 phases and current for L1. Below the display are indicators for Power, Over-voltage (>V), Under-voltage (<V), and Over-current (>I). Control buttons include 'SET' (Menu key), 'Digit+/Up', 'Digit-/Down', and 'Manual ON/OFF' (Power button).

The digital display provides real-time voltage readings for each phase (L1, L2, L3) and the current for L1. Status indicators alert you to the operational state and any detected faults:

  • Moc: Indikace výstupu.
  • >V: Voltage indikace.
  • <V: Pod voltage indikace.
  • >Já: Indikace nadproudu.

Control buttons allow for parameter settings and manual operation:

  • SOUBOR: Menu key for accessing settings.
  • Digit+/Up: Increases value or navigates up in menus.
  • Digit-/Down: Decreases value or navigates down in menus.
  • Manuální ZAP/VYP: Power button for manual control.

4. Nastavení a instalace

The ATS is designed for standard DIN rail mounting. Ensure sufficient space for ventilation and wiring connections.

4.1. Schéma zapojení

Wiring diagram for EARU Electric 3-Phase ATS showing input and output connections

Popis obrázku: A detailed wiring diagram illustrates the connection points for the ATS. The top terminals are labeled 'IN' with connections for N, L1, L2, L3. The bottom terminals are labeled 'OUT' with connections for N and L1. The diagram shows how to connect the three-phase input to the ATS and how a single-phase load (L1 and N) is connected to the output, with internal connections for phase monitoring and switching.

Follow the wiring diagram carefully. Incorrect wiring can lead to device malfunction or electrical hazards.

  • Connect the incoming three-phase power supply (N, L1, L2, L3) to the 'IN' terminals.
  • Connect the single-phase load (N, L1) to the 'OUT' terminals. The ATS will manage the phase transfer for the L1 output.
  • Ensure all connections are secure and tightened to prevent loose contacts and overheating.

4.2. Počáteční zapnutí

After completing the wiring, restore power to the system. The ATS will power on and begin monitoring the phases. The digital display will show the current voltage readings for each phase. If all phases are stable and within acceptable limits, the ATS will provide power to the output.

5. Návod k obsluze

The ATS operates automatically, but you can adjust its protection parameters to suit your specific requirements.

5.1. Understanding the Display and Indicators

The digital display continuously shows the real-time voltage of each phase (L1, L2, L3) and the current on L1. The indicator lights provide quick visual feedback on the device's status and any detected anomalies.

Close-up of EARU Electric 3-Phase ATS digital display showing voltage a aktuální hodnoty

Popis obrázku: Detailní záběr view of the ATS digital display. It shows '220V' for L1, L2, and L3, and '63.0A' for L1 current. Below these readings are small indicator icons for Power, >V (Over-voltage), <V (Under-voltage), and >I (Over-current).

5.2. Adjusting Protection Parameters

Use the 'SET' button to enter the parameter setting mode. Use the 'Digit+/Up' and 'Digit-/Down' buttons to navigate through settings and adjust values. Press 'SET' again to confirm and save changes.

Adjustable Protection Parameters
ParametrRozsah nastaveníVýchozí nastavení
Rozsah nastavení ochrany proti nadproudu1-63A/100A30A
Continuous Over Current Protection Times0-20krátVYPNUTO
Přes VoltagRozsah nastavení ochrany e230-300V270V
Přes VoltagRozsah nastavení obnovení ochrany e225-295V265V
Pod svtagRozsah nastavení ochrany e140-210V170V
Pod svtagRozsah nastavení obnovení ochrany e145-215V175V
svtage & Current Protection Recover Delay1-500s30s

5.3. Automatic Phase Transfer

The ATS automatically monitors the three input phases (L1, L2, L3). If a phase failure or significant voltage imbalance (over/under voltage) is detected on the currently supplying phase, the device will automatically transfer the single-phase output load to a healthy, stable phase within the same supply. This process is designed to be seamless and rapid, minimizing power interruption to connected equipment.

5.4. Automatic Recovery

Once the primary phase recovers and stabilizes, the ATS will intelligently switch the load back to the primary source, ensuring optimal power distribution and preventing equipment damage from unstable power. The recovery delay can be configured as per your operational needs.

6. Údržba

The EARU Electric ATS is designed for minimal maintenance. However, periodic checks are recommended to ensure optimal performance and longevity.

  • Čištění: Udržujte zařízení čisté a bez prachu a nečistot. K čištění používejte suchý, měkký hadřík. Nepoužívejte tekuté čisticí prostředky.
  • Kontroly připojení: Pravidelně kontrolujte všechna kabelová spojení, abyste se ujistili, že jsou pevná a bez koroze.
  • Podmínky prostředí: Zajistěte, aby provozní prostředí zůstalo v rámci specifikovaného rozsahu teploty a vlhkosti.

7. Řešení problémů

If you encounter issues with your ATS, refer to the following common problems and solutions:

Průvodce řešením problémů
ProblémMožná příčinaŘešení
Žádný výstupní výkonNo input power; all phases unstable; device in fault state.Check incoming power supply. Verify all phases are stable. Check fault indicators.
">V" or "<V" indicator litVoltage nebo pod-objtage detected on a phase.Zkontrolujte vstupní objtage stability. The ATS will automatically transfer if another phase is healthy.
">I" indicator litOver-current detected on the output.Reduce load on the output. Check for short circuits in the connected equipment.
Device not transferring phasesNo healthy alternative phase available; transfer delay setting too long.Ensure at least one healthy phase is present. Check and adjust the transfer delay settings.
Digitální displej nefungujeNo power to the device; internal fault.Check power supply. If power is present and display is off, contact support.

For issues not covered here, please contact EARU customer support.

8. Specifikace

Detailed specifications and dimensions of EARU Electric 3-Phase ATS

Popis obrázku: This image displays the physical dimensions of the ATS (90mm width, 96mm height, 66mm depth) and a table of detailed technical specifications, including current rating, voltage, frequency, and various protection setting ranges.

FunkceDetail
ZnačkaEARU
Číslo modeluEARU-1012
Provozní režimZAPNUTO VYPNUTO
Aktuální hodnocení63 Amps
Provozní svtage440 Volts (AC 3*220V (N-L1/L2/L3))
Jmenovitá frekvence50/60 Hz
Typ kontaktuNormálně otevřeno
Typ konektoruStandard DIN rail 63A
Typ obvodu4-cestný
Kontaktní materiálMěď
Rozsah nastavení ochrany proti nadproudu1-63A/100A (Default 30A)
Continuous Over Current Protection Times0-20 Times (Default OFF)
Přes VoltagRozsah nastavení ochrany e230–300 V (výchozí 270 V)
Přes VoltagRozsah nastavení obnovení ochrany e225–295 V (výchozí 265 V)
Pod svtagRozsah nastavení ochrany e140–210 V (výchozí 170 V)
Pod svtagRozsah nastavení obnovení ochrany e145–215 V (výchozí 175 V)
svtage & Current Protection Recover Delay1–500 s (výchozí 30 s)
Hmotnost položky450 g
Rozměry balení15 x 15 x 15 cm
Země původuIndie

9. Záruka a podpora

9.1. Informace o záruce

The EARU Electric 3-Phase Auto Transfer Switch (ATS) comes with a 1letá záruka výrobce od data nákupu. Tato záruka se vztahuje na vady materiálu a zpracování při běžném používání. Nevztahuje se na škody způsobené nesprávnou instalací, zneužitím, nehodami nebo neoprávněnými úpravami.

9.2. Zákaznická podpora

For technical assistance, warranty claims, or any questions regarding your EARU Electric ATS, please contact your retailer or the manufacturer directly. Ensure you have your product model number (EARU-1012) and proof of purchase available when contacting support.

© 2023 EARU Electric. Všechna práva vyhrazena.