This manual provides essential information for the safe and efficient installation, operation, and maintenance of your Asurity by Diversitech CP-22LPT Low Profile Condensate Pump. This pump is designed to automatically evacuate condensate or water discharge from HVACR equipment, offering a vertical lift capability of up to 22 feet. Its low-profile design makes it suitable for installations in tight spaces.

Bezpečnostní informace

Před instalací a provozem si pečlivě přečtěte všechny pokyny. Nedodržení těchto pokynů může vést k poškození majetku, zranění osob nebo smrti.

  • Elektrické nebezpečí: Disconnect power before servicing. This unit operates on 110 Volts. Ensure all electrical connections comply with local codes.
  • Vodní hazard: This pump handles water. Ensure proper drainage and prevent water damage.
  • Instalace: Install the pump in a location where it is accessible for maintenance and inspection.
  • Zamýšlené použití: Use this pump only for its intended purpose of evacuating condensate from HVACR equipment.
  • Seznam UL: This product is UL listed, meeting electrical and mechanical safety standards for water pumps.

Obsah balení

Před zahájením instalace ověřte, zda jsou všechny položky přítomny:

  • Asurity by Diversitech CP-22LPT Condensate Pump
  • 20 ft Clear Vinyl Tubing
  • 4 ft Safety Switch Wire (pigtail)

Konec produktuview

The Asurity CP-22LPT condensate pump features a compact design with advanced functionalities for reliable condensate removal.

Asurity CP-22LPT Condensate Pump with Clear Tubing

Obrázek 1: The Asurity CP-22LPT low profile condensate pump shown with the included clear vinyl tubing. The pump features a red base and a black motor housing with ventilation slots and an outlet port.

Asurity CP-22LPT Condensate Pump with Tubing and Safety Switch Wire

Obrázek 2: Shora dolů view of the Asurity CP-22LPT condensate pump, accompanied by the coiled clear vinyl tubing and the yellow safety switch wire. This image highlights all primary components included with the unit.

Strana View of Asurity CP-22LPT Condensate Pump

Obrázek 3: A side perspective of the Asurity CP-22LPT condensate pump, illustrating its low-profile design. This view emphasizes the compact dimensions suitable for installation in confined spaces.

Klíčové vlastnosti:

  • LED Status Indicator Lights (Power, Run, Alarm)
  • Vibrace Dampening System for quiet operation
  • Integrated Safety Switch with 4 feet of wire for air-handler shutdown
  • Nízký profile design for tight installations
  • Metal mounting tabs for secure installation
  • Four inlet holes (with 3 poly covers for unused ports)
  • Float switch and duckbill-style check valve

Nastavení a instalace

Proper installation is crucial for the pump's performance and longevity. Ensure all local electrical and plumbing codes are followed.

  1. Umístění: Position the pump on a level surface near the HVACR unit. The low-profile design is ideal for tight spaces. Utilize the vibration dampening feet and metal mounting tabs for secure placement.
  2. Připojení vstupu kondenzátu: Connect the condensate drain line from the HVACR unit to one of the pump's inlet holes. The pump has four inlet holes; seal any unused inlets with the provided poly covers.
  3. Připojení výtlačného potrubí: Connect the 20 ft clear vinyl tubing to the pump's discharge outlet. Route the tubing upwards, ensuring it does not exceed the pump's 22 ft vertical lift capability, and then to a suitable drain point. Avoid kinks or sharp bends in the tubing. The integrated duckbill-style check valve prevents backflow.
  4. Elektrické připojení: Connect the pump to a dedicated 110V power supply. Ensure the power source is off before making connections.
  5. Připojení bezpečnostního spínače: Connect the 4 ft safety switch wire (pigtail) to the air-handler's shutdown circuit. This feature is designed to shut down the HVACR unit if the pump fails or the water level rises too high, preventing overflow. Refer to your HVACR unit's manual for specific wiring instructions for the safety switch.
  6. Testování: After installation, manually pour water into the pump's reservoir to verify proper operation. The pump should activate, discharge the water, and then shut off. Check for any leaks.

Návod k obsluze

The Asurity CP-22LPT condensate pump operates automatically once properly installed and powered.

  • When condensate water enters the pump's reservoir and reaches a predetermined level, the internal float switch activates the pump.
  • The pump will then discharge the water through the connected vinyl tubing to the designated drain.
  • Once the water level drops, the float switch deactivates the pump.
  • LED indikátory:
    • Výkon (Příkon): Illuminates when the pump is receiving electrical power.
    • Běh: Illuminates when the pump motor is actively discharging water.
    • Alrm (Alarm): Illuminates if the water level rises to the high-level alarm switch, indicating a potential issue and activating the safety shutdown circuit.

Údržba

Pravidelná údržba zajišťuje optimální výkon a prodlužuje životnost vašeho kondenzačního čerpadla.

  • Měsíční kontrola: Check the pump reservoir for sludge, mold, or debris. Clean as necessary.
  • Čištění: Disconnect power before cleaning. Remove the pump cover and clean the reservoir with a mild detergent and water. Ensure the float switch moves freely.
  • Výtlačné potrubí: Inspect the vinyl tubing for blockages, kinks, or leaks. Clear any obstructions.
  • Vstupní porty: Ensure inlet ports are clear of debris.

Odstraňování problémů

Běžné problémy a jejich řešení naleznete v následující tabulce.

Problém Možná příčina Řešení
Čerpadlo neběží No power; Clogged inlet/outlet; Stuck float switch; Motor failure Check power supply; Clear blockages; Inspect/clean float switch; Contact support if motor fails
Čerpadlo běží nepřetržitě Stuck float switch; Leak in discharge line; Pump undersized for flow rate Inspect/clean float switch; Check for leaks; Verify pump capacity meets demand
Water overflow / Alarm LED on Pump failure; Clogged discharge line; Safety switch activated Check pump operation; Clear discharge line; Investigate cause of high water level
Nadměrný hluk/vibrace Debris in pump; Improper mounting; Worn motor bearings Clean pump; Ensure secure mounting; Contact support for motor issues

Specifikace

Funkce Detail
Značka Diversitech (Asurity)
Číslo modelu CP-22LPT
svtage 110 voltů
Zdroj napájení Elektrický kabel
Maximální zdvih 22 stop
Maximální průtok 1.6 galonu za minutu
Rozměry produktu 12 cm D x 6.75 cm Š x 6 cm V
Hmotnost položky 5.41 libry
Materiál Plast
Barva Červená Černá
Zahrnuté komponenty Condensate Pump, 20ft clear vinyl tubing, 4ft safety switch wire (pigtail)
Certifikace Seznam UL

Záruka a podpora

For warranty information or technical support, please contact Diversitech customer service. Keep your purchase receipt for warranty claims.

Výrobce: Diversitech

Webmísto: www.diversitech.com

Kontakt: Viz pokyny výrobce webstránky s aktuálními kontaktními informacemi.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.