Tyenaza ETCR2100A+

Tyenaza ETCR2100A+ Digital Clamp Resistance Tester User Manual

Model: ETCR2100A+

1. Úvod

This manual provides essential instructions for the safe and effective operation of the Tyenaza ETCR2100A+ Digital Clamp Resistance Tester. This device is designed for accurate measurement of grounding resistance and circuit resistance, featuring a dustproof and shockproof structure for reliable performance in various industrial and departmental settings.

Please read this manual thoroughly before using the instrument to ensure proper handling and to prevent damage or injury.

Tyenaza ETCR2100A+ Digital Clamp Odporový tester

Image 1.1: The Tyenaza ETCR2100A+ Digital Clamp Resistance Tester, showing its overall design with the clamp jaw and control panel.

2. Bezpečnostní informace

Always observe the following safety precautions to avoid electric shock, injury, or damage to the instrument:

  • Nepoužívejte přístroj, pokud se jeví poškozený nebo pokud nefunguje abnormálně.
  • Před použitím se ujistěte, že je přihrádka na baterie bezpečně uzavřena.
  • Nepokoušejte se měřit napětí v obvodech nad stanovenou mezní hodnotou.tage limits (CAT III 150V).
  • Avoid using the instrument in wet environments or during thunderstorms.
  • Refer to qualified personnel for any repairs or servicing.
  • Keep the instrument away from strong magnetic fields and electric fields exceeding specified limits.

3. Obsah balení

Ověřte, zda jsou v balení přítomny všechny položky:

  • 1 x ETCR2100A+ Digital Clamp Odporový tester
  • 1 x Accessory (likely a test ring or similar calibration aid)
  • 1 x Uživatelská příručka (tento dokument)
  • 1 x úložný box

Note: 1.5V AA batteries (x4) are required and are not included in the package.

ETCR2100A+ Digital Clamp Resistance Tester with included accessory

Image 3.1: The ETCR2100A+ tester shown with a standard test ring, which is typically included as an accessory for calibration or verification.

4. Vlastnosti produktu

The ETCR2100A+ Digital Clamp Resistance Tester offers the following key features:

  • Multifunkční displej: Resistance and current values are displayed simultaneously on a new black luxury screen.
  • Vysoká přesnost: Microprocessor-controlled for precise grounding resistance detection, utilizing fast filtering technology to minimize interference.
  • Správa dat: Features real-time clock, data storage for up to 99 sets, and data retrieval capabilities.
  • Zvukový a vizuální alarm: "Beep beep beep" alarm sound with adjustable threshold settings for resistance (1-199 Ω) and current (1-499mA).
  • Automatické funkce: Automatic shutdown and fully automatic gear shifting for ease of use.
  • Robustní design: Shockproof and dustproof structure, suitable for demanding industrial environments.
  • Široká aplikace: Ideal for telecommunications, power, meteorology, computer rooms, oil fields, power distribution lines, tower transmission lines, gas stations, factory grounding grids, and lightning rod systems.
Detailní záběr view z třamp jaws of the ETCR2100A+ tester

Obrázek 4.1: Detailní záběr view of the robust clamp jaws, highlighting the double insulation and structural features designed for durability and safety.

5. Nastavení

5.1 Instalace baterie

The ETCR2100A+ requires four (4) 1.5V AA batteries (not included).

  1. Locate the battery compartment cover on the back of the instrument.
  2. Use a suitable tool (if necessary) to open the battery compartment.
  3. Insert four 1.5V AA batteries, ensuring correct polarity (+/-) as indicated inside the compartment.
  4. Bezpečně zavřete kryt bateriového prostoru.

5.2 Počáteční zapnutí

Po vložení baterie stiskněte tlačítko ON/OFF button to power on the device. The LCD display will illuminate, indicating the device is ready for use.

6. Návod k obsluze

6.1 Základní měření

To perform a grounding resistance test:

  1. Ujistěte se, že je přístroj zapnutý.
  2. Otevřete třamp čelisti stisknutím spouště.
  3. Umístěte třamp around the grounding conductor or circuit to be measured. Ensure the jaws are fully closed around the conductor.
  4. The resistance value will be displayed on the LCD screen. The device features fully automatic shifting.
  5. The single measurement time is approximately 0.5 seconds.
ETCR2100A+ tester clamping an insulated ground wire

Image 6.1: The ETCR2100A+ tester shown clamping an insulated ground wire, demonstrating its capability to accurately test even insulated conductors.

6.2 Single Point Grounding System, Auxiliary Measurement

For single point grounding systems where direct clamp measurement of the lead wire is not feasible, auxiliary methods can be used. The two-point method is illustrated below:

Diagram illustrating the two-point auxiliary measurement method for single point grounding systems

Image 6.2: Diagram showing the two-point method for auxiliary grounding resistance measurement. It depicts a grounding rod (RA) connected to a single point, with a wire extending to a natural grounding point (e.g., water pipe, buried metal) for measurement.

Chcete-li použít tuto metodu:

  • Identify a natural grounding point with a low resistance value near the grounding point to be measured. Examples include a water pipe, fire hydrant, or other deeply buried metal structure.
  • Connect a wire from the point to be measured to this auxiliary grounding point.
  • Clamp the ETCR2100A+ around the connecting wire to perform the measurement.
ETCR2100A+ Digital Clamp Resistance Tester in an industrial substation environment

Image 6.3: The ETCR2100A+ tester positioned in an industrial substation, illustrating a typical application environment for grounding resistance measurement.

6.3 Data Storage and Retrieval

The instrument can store up to 99 sets of measurement data.

  • To store data: After a measurement, press the MEM button to save the current reading.
  • To retrieve data: Press the MEM button repeatedly to cycle through stored data.

6.4 Funkce alarmu

The ETCR2100A+ features an audible and visual alarm for out-of-range measurements.

  • To activate/deactivate the alarm: Press the AL tlačítko.
  • To set alarm thresholds: Refer to the device's on-screen menu or specific instructions for setting resistance (1-199 Ω) and current (1-499mA) alarm limits.
Hand holding the ETCR2100A+ Digital Clamp Odporový tester

Image 6.4: A hand holding the ETCR2100A+ tester, demonstrating its ergonomic design and ease of handling during operation.

7. Údržba

7.1 Čištění

Wipe the instrument's exterior with a soft, damp cloth. Do not use abrasive cleaners or solvents. Ensure the device is powered off before cleaning.

7.2 Skladování

When not in use for extended periods, remove the batteries to prevent leakage. Store the instrument in its provided storage box in a cool, dry place, away from direct sunlight and extreme temperatures.

7.3 Kalibrace

Regular calibration by qualified personnel is recommended to maintain measurement accuracy, especially after prolonged use or if accuracy is suspected to be compromised.

8. Řešení problémů

ProblémMožná příčinaŘešení
Zařízení se nezapne.Vybité nebo nesprávně vložené baterie.Vyměňte baterie za nové 1.5V AA baterie a dbejte na správnou polaritu.
Nepřesné údaje.Jaws not fully closed; interference from external fields; dirty jaws; need for calibration.Ensure jaws are fully closed. Move away from strong magnetic/electric fields. Clean jaws. Consider professional calibration.
Budík zní nepřetržitě.Measurement exceeds set alarm threshold.Check the measured value against the set alarm limits. Press the AL button to silence or deactivate the alarm.
Displej je prázdný nebo bliká.Low battery power; environmental conditions (extreme temperature/humidity).Replace batteries. Operate within specified temperature and humidity ranges (-20 ℃ to 55 ℃; 10% RH to 90% RH).

9. Specifikace

ModelETCR2100A+
FunkceGrounding resistance test, circuit resistance test, leakage current test
Rozsah odporu0.01 Ω až 200 Ω
Rozlišení odporu0.001 Ω
Aktuální rozsahNone (for leakage current test, the range is 1-499mA for alarm setting)
Ukládání dat99 sady
Alarm Threshold Setting Range (Resistance)1-199 Ω
Alarm Threshold Setting Range (Current)1-499 mA
Pracovní teplota a vlhkost-20 ℃ to 55 ℃; 10% RH to 90% RH
LCD displej4 digit LCD digital display
Velikost displejeApprox. 47 x 28.5mm / 1.85 x 1.12in (L x W)
Jaw Size (Round)Approx. 32mm / 1.26in diameter
Jaw Opening Size (Long)Přibližně 32 mm / 1.26 palce
Clamp Size (Long Jaw)Přibližně 260 × 90 × 56 mm / 10.24 × 3.54 × 2.2 palce
Úroveň ochranyDvojitá izolace
Strukturální vlastnostiClamp shaped CT
Řazení převodových stupňůFully automatic shifting
Vnější magnetické pole<40A/m
Vnější elektrické pole<1V/m
Single Measurement Time0.5 sekund
Resistance Measurement FrequencyGreater than 1KHz
Tested Current Frequency50/60Hz automatic
Napájení4 x 1.5V AA baterie (nejsou součástí balení)
MateriálABS
Hmotnost položky2.13 kg / 4.69 liber

10. Záruka a podpora

Pro informace o záruce, technickou podporu nebo servisní dotazy se prosím obraťte na svého prodejce nebo přímo na výrobce. Uschovejte si účtenku jako doklad o koupi.

Manufacturer: Tyenaza

© 2023 Tyenaza. All rights reserved.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.