Service First CAP02328_ver1
Návod k použití
Service First OEM Start Capacitor
1. Úvod
This manual provides essential information for the proper handling, installation, and maintenance of the Service First OEM Start Capacitor, model CAP02328_ver1. This component is designed for use in Trane and American Standard HVAC systems.
A start capacitor provides a temporary electrical boost to the motor during startup, helping it overcome initial inertia and reach operating speed quickly. It is a critical component for the efficient and reliable operation of many electrical motors, particularly in HVAC applications.
2. Bezpečnostní informace
WARNING: Electrical Hazard. Risk of electric shock or injury.
- Always disconnect power to the unit before attempting any installation, maintenance, or troubleshooting.
- Capacitors can store a dangerous electrical charge even after power is disconnected. Always discharge the capacitor before handling. Use a properly insulated screwdriver with a metal shaft to short the terminals, or use a capacitor discharge tool.
- Používejte vhodné osobní ochranné prostředky (OOP), včetně izolačních rukavic a ochranných brýlí.
- Installation and service should only be performed by qualified and licensed HVAC technicians.
- Ensure the replacement capacitor matches the specifications (uF/MFD and VAC) of the original component.
3. Specifikace produktu
| Specifikace | Hodnota |
|---|---|
| Číslo modelu | CAP02328_ver1 |
| Značka | Service First (OEM Component by CAPCOM) |
| Kapacita | 196 uF (MFD) +/- 5 uF |
| svtage Hodnocení | 330 VAC |
| Tvar | Kolo |
| Vlastnosti | Includes Resistor |
| Materiál | Měď |
| Hmotnost položky | 1 libra |
| První k dispozici | 19. srpna 2020 |

Figure 3.1: Approximate dimensions of the capacitor. Note: Dimensions are subject to change without notice.
4. Instalace a výměna
This section outlines the general procedure for replacing a start capacitor. Always refer to the specific service manual for your HVAC unit for detailed instructions and safety precautions.
- Odpojení napájení: Locate the main power switch for the HVAC unit (typically at the outdoor condenser unit or indoor furnace/air handler) and turn it OFF. For added safety, turn off the corresponding circuit breaker at the electrical panel. Verify power is off using a voltage tester.
- Přístupový kondenzátor: Remove the access panel(s) on the HVAC unit to expose the electrical components, including the capacitor.
- Vybíjecí kondenzátor: Before touching the capacitor, discharge any stored electrical energy. Use an insulated screwdriver with a metal shaft to short the terminals of the old capacitor. Hold the screwdriver by the insulated handle and touch the metal shaft across both terminals simultaneously. A spark may occur. Repeat this process several times to ensure full discharge.
- Poznámka k zapojení: Carefully observe and note the wiring connections to the old capacitor. Take a photograph or draw a diagram of the wiring before disconnecting any wires. Capacitors typically have two terminals for start capacitors.
- Odstranění starého kondenzátoru: Disconnect the wires from the old capacitor. Loosen any clamps or straps holding the capacitor in place and remove it from the unit.
- Instalace nového kondenzátoru: Place the new Service First OEM Start Capacitor (model CAP02328_ver1) into the mounting bracket. Secure it with clamps or straps if applicable.
- Připojení kabeláže: Reconnect the wires to the new capacitor exactly as they were connected to the old one, referring to your diagram or photograph. Ensure connections are secure.
- Znovu sestavte a otestujte: Replace all access panels. Restore power to the HVAC unit at the circuit breaker and main power switch. Test the unit's operation to ensure the motor starts correctly.

Figure 4.1: Service First OEM Start Capacitor (CAP02328_ver1) and packaging.

Figure 4.2: Close-up of the capacitor showing specifications label.
5. Provoz
The Service First OEM Start Capacitor (CAP02328_ver1) is an electrical component designed to provide a temporary surge of current to the motor's start winding during the initial phase of operation. This surge creates a stronger magnetic field, allowing the motor to overcome its inertia and begin rotating. Once the motor reaches approximately 75% of its operating speed, a centrifugal switch (or electronic equivalent) typically disconnects the start capacitor from the circuit, and the motor continues to run on its run winding.
This capacitor is specifically rated at 196 uF MFD and 330 VAC, ensuring compatibility with systems requiring these specifications for proper motor startup.
6. Údržba
Start capacitors are generally sealed units and do not require routine maintenance. However, periodic inspection during HVAC system servicing is recommended. A qualified technician should check for:
- Fyzické poškození: Look for signs of swelling, bulging, leaks, or corrosion on the capacitor casing. Toto jsou indikátory selhání.
- Přehřívání: Check for discoloration or burnt smells around the capacitor, which can indicate overheating.
- Proper Function: A technician can test the capacitance (uF/MFD) and ESR (Equivalent Series Resistance) of the capacitor using a specialized meter to ensure it is within specifications.
If any issues are detected, the capacitor should be replaced by a qualified professional.
7. Řešení problémů
A failing start capacitor can manifest in several ways. If you experience any of the following symptoms, it may indicate a capacitor issue. Always consult a qualified HVAC technician for diagnosis and repair.
| Příznak | Možná příčina (souvisí s kondenzátorem) | Akce (doporučeno profesionály) |
|---|---|---|
| Motor hums but does not start (or starts slowly) | Weak or failed start capacitor | Test and replace capacitor if faulty. |
| Circuit breaker trips on startup | Shorted capacitor | Test and replace capacitor. |
| Visible bulging, leaking, or burning on capacitor | Porucha kondenzátoru | Nutná okamžitá výměna. |
| Motor běží horký | Capacitor not disconnecting or incorrect capacitance | Test capacitor and motor circuit. |
Důležité: Do not attempt to repair a faulty capacitor. Always replace it with a new one that matches the original specifications.

Obrázek 7.1: Nahoře view of the capacitor terminals and resistor.
8. Kompatibilita a náhrada
The Service First OEM Start Capacitor, model CAP02328_ver1 (CPT02328 / CPT-2328), is a direct replacement for various Trane and American Standard units and supersedes several older part numbers. It is crucial to verify that the required capacitance (196 uF MFD) and voltage (330 VAC) match your existing capacitor or system requirements.
This capacitor replaces or supersedes the following part numbers:
- CPT0950, CPT950, CPT-0950, CPT00950
- CPT2328, CPT02328, CPT-2328
- CPT01808, CPT1808, CPT-1808
- CPT00320, CPT-320, CPT0320
- 175-216, 176-216
- And other start capacitors with matching specifications (196 uF MFD, 330 VAC).
Commonly found in the following American Standard & Trane Units (partial list):
- 2A6H8030B1000AA, 2A6H8030B1000BA, 2A6H8030C1000AA
- 2A6H8036B1000BA, 2A6H8036C1000AA
- 2A6H8048B1000BA, 2A6H8048C1000AA
- 2A6H8060B1000AA, 2A6H8060B1000BA, 2A6H8060C1000AA
- 2A7A8030A1000AA, 2A7A8030B1000BA, 2A7A8030C1000AA
- 2A7A8036B1000BA, 2A7A8036C1000AA
- 2A7A8048B1000BA, 2A7A8048C1000AA
- 2A7A8060A1000AA, 2A7A8060B1000AA, 2A7A8060C1000AA
- 2TTB3042A1000NA, 2TTB3042A1S00AA, 2TTB3042A1SE0AA
- 2TTZ9030A1000AA, 2TTZ9030A1000AB, 2TTZ9030B1000AA
- 2TTZ9030B1000BA, 2TTZ9030C1000AA, 2TTZ9036B1000BA
- 2TTZ9036C1000AA, 2TTZ9048B1000BA, 2TTZ9048C1000AA
- 2TTZ9060A1000AA, 2TTZ9060A1000AB, 2TTZ9060B1000AA
- 2TTZ9060B1000BA, 2TTZ9060C1000AA, 2TWZ9030A1000AA
- 2TWZ9030A1000AB, 2TWZ9030A1000AC, 2TWZ9030B1000AA
- 2TWZ9030B1000BA, 2TWZ9030C1000AA, 2TWZ9036B1000BA
- 2TWZ9036C1000AA, 2TWZ9048B1000BA, 2TWZ9048C1000AA
- 2TWZ9060A1000AA, 2TWZ9060A1000AC, 2TWZ9060B1000AA
- 4A6Z0060A1000AA, 4A6Z0060A1000BA, 4A6Z0060A1000CA
- 4A7A3036D1000AA, 4A7A3036D1000AB, 4A7B3036D1000AA
- 4A7M3036A1000AA, 4A7Z0024A1000AA, 4A7Z0024A1000BA
- 4A7Z0024A1000BB, 4A7Z0024A1000CA, 4A7Z0024A1000CB
- 4A7Z0036A1000AA, 4A7Z0036A1000BA, 4A7Z0036A1000BB
- 4A7Z0036A1000CA, 4A7Z0036B1000AA, 4A7Z0048A1000AA
- 4A7Z0048A1000BA, 4A7Z0048A1000CA, 4A7Z0048B1000AA
- 4A7Z0060A1000AA, 4A7Z0060A1000BA
For a complete list of compatible units, refer to the product listing or consult with a qualified HVAC technician.
9. Záruka a podpora
For information regarding warranty coverage for the Service First OEM Start Capacitor (model CAP02328_ver1), please refer to the original purchase documentation or contact the vendor directly. Warranty terms typically cover manufacturing defects.
For technical support or assistance with installation and troubleshooting, it is recommended to contact a qualified and licensed HVAC professional. Service First does not provide direct end-user technical support for component installation.
S obecnými dotazy ohledně produktů můžete navštívit Service First brand page on Amazon.
Ask a question about this manual
Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.