This manual provides essential instructions for the safe and effective operation of the Benning IT 115 True RMS Installation Tester. This multifunction device is designed for testing electrical installations in accordance with international standards such as DIN VDE 0100-600, IEC 60364-6, DIN VDE 0105-100, and EN 50110. Please read this manual thoroughly before using the instrument.

2. Bezpečnostní informace

WARNING: Electrical shock hazard. Improper use of this instrument can result in injury or death. Always follow safety precautions.

  • Always disconnect all test leads and switch off the instrument before opening the battery/fuse cover.
  • Do not open the battery compartment if hazardous voltage je přítomno.
  • Ensure the instrument is in good working condition before use. Do not use if damaged.
  • Observe all local and national safety regulations for electrical work.
  • Používejte pouze dodané příslušenství nebo schválené náhradní díly.
  • Nepokoušejte se měřit objemtages or currents exceeding the instrument's specified limits.

3. Konec produktuview

The Benning IT 115 is a robust installation tester featuring a backlit graphic display and intuitive controls. It is designed for comprehensive electrical installation testing.

Benning IT 115 True RMS Installation Tester front view

Obrázek 3.1: Přední strana view of the Benning IT 115 Installation Tester, showing the display, rotary switch, and control buttons.

Mezi klíčové komponenty patří:

  • Graphic Display: Backlit screen for clear readings and connection diagrams.
  • Otočný přepínač: Selects measurement functions (e.g., R_ISO, R_LOW, Z_L-N/L, Z_L-PE, FI/RCD, SETTINGS).
  • Ovládací tlačítka: Navigation, TEST, ON/OFF, HELP, ESC.
  • Test Lead Connections: Input terminals for test leads.
  • LED indikátory: Green/red LEDs provide quick pass/fail indications.
Benning IT 115 True RMS Installation Tester rear view s přihrádkou na baterie

Obrázek 3.2: Zadní view of the Benning IT 115, showing the battery compartment and safety warnings.

4. Nastavení

4.1. Instalace a nabíjení baterie

The Benning IT 115 operates on 6 rechargeable NiMH AA batteries. A charger is included for convenience.

  1. Ensure the instrument is switched off and all test leads are disconnected.
  2. Open the battery compartment cover on the rear of the device (refer to Figure 3.2).
  3. Vložte 6 NiMH AA baterií a dbejte na správnou polaritu.
  4. Bezpečně zavřete kryt bateriového prostoru.
  5. Connect the charger to the instrument's charging port and to a suitable power outlet to charge the batteries. The integrated battery charging function will manage the charging process.

NOTE: Do not use non-rechargeable alkaline batteries with the integrated charging function.

4.2. Připojení měřicích kabelů a příslušenství

The device comes with a set of accessories for various measurements.

Benning IT 115 accessories including carrying case, test leads, probes, and batteries

Figure 4.1: Included accessories: carrying case, test leads, probes, crocodile clips, and rechargeable batteries.

  • Connect the test cable with the protective contact plug for standard outlet measurements.
  • For other measurements, use the 3-conductor universal cable (1.5 m length) with the provided test probes or crocodile clips as required by the specific test.
  • Ensure all connections are secure before performing any tests.

5. Návod k obsluze

The Benning IT 115 offers a range of measurement functions accessible via the rotary switch and control buttons. The graphic display provides clear readings and a help function with connection diagrams.

5.1. Zapnutí/vypnutí

Stiskněte tlačítko ON/OFF button to switch the instrument on or off.

5.2. Insulation Resistance Measurement (R_ISO)

Measures insulation resistance between 0.01 MOhm and 1000 MOhm.

  1. Otočte otočný přepínač do polohy R_ISO.
  2. Select the desired nominal test voltage (50V, 100V, 250V, 500V, 1000V) using the navigation buttons.
  3. Connect the test leads to the circuit under test as indicated by the on-screen help diagram.
  4. Stiskněte tlačítko TEST tlačítko pro zahájení měření.
  5. The result will be displayed, and the green/red LEDs will indicate pass/fail based on set limits.

5.3. Low-Ohm Resistance Measurement (R_LOW)

Measures low resistance from 0.01 Ohm to 2000 Ohms, typically for protective conductor continuity.

  1. Otočte otočný přepínač do polohy R_LOW.
  2. Connect the test leads to the protective conductor.
  3. Stiskněte tlačítko TEST button. The instrument uses a 200 mA test current with polarity reversal and a 7 mA test current for continuity.
  4. Observe the displayed resistance value.

5.4. Earth Resistance Measurement (R_E)

Measures earth resistance using the 3-conductor method (requires optional earthing kit 044113).

  1. Otočte otočný přepínač do polohy R_E.
  2. Connect the optional earthing kit according to the on-screen diagram.
  3. Stiskněte tlačítko TEST tlačítko.
  4. The earth resistance value will be displayed.

5.5. Loop and Line Impedance Measurement (Z_L-N/L, Z_L-PE)

Measures loop impedance (0.01 Ohm - 10 kOhm) for fault current path and short-circuit current determination.

  • Line Impedance (Z_L-N/L): Measures impedance between Line and Neutral or Line and Line, including voltage drop and short-circuit current.
  • Loop Impedance (Z_L-PE): Measures impedance between Line and Protective Earth without tripping RCD/FI, including short-circuit current.
  1. Otočte otočný přepínač do polohy Z_L-N/L or Z_L-PE.
  2. Connect the test leads to the appropriate points in the circuit.
  3. Stiskněte tlačítko TEST tlačítko.
  4. The impedance value and calculated short-circuit current will be displayed.

5.6. RCD/FI Test

Tests Residual Current Devices (RCDs) / Fault Current Circuit Breakers (FI) of types AC, A, and F, including standard and delayed (S) types.

  • Tests include automatic test sequences, touch voltage, trip time, and trip current (ramp test).
  • Features an RCD/FI analysis function.
  1. Otočte otočný přepínač do polohy FI/RCD.
  2. Select the RCD type (AC, A, F) and nominal current using the navigation buttons.
  3. Connect the test leads to the circuit protected by the RCD.
  4. Stiskněte tlačítko TEST button to start the test sequence.
  5. The results (trip time, trip current, touch voltage) se zobrazí.

5.7. Rotary Field Test

Determines the phase sequence in three-phase systems.

  1. Turn the rotary switch to the rotary field test setting (refer to the device's specific icon).
  2. Connect the test leads to the three phases.
  3. The display will indicate the phase sequence.

5.8. svtage a Měření frekvence

Měří AC/DC objtage a frekvence.

  • svtage Rozsah: 1 V - 550 V AC/DC (True RMS measurement).
  • Frekvenční rozsah: 0 Hz - 500 Hz.
  1. The instrument continuously monitors line voltage.
  2. Připojte testovací vodiče k zvtage zdroj.
  3. Voltage and frequency will be displayed automatically.

5.9. Help Function

The integrated help function provides connection diagrams and guidance for each measurement. Press the POMOC button to access it.

6. Údržba

6.1. Čištění

Clean the instrument regularly with a soft, damp tkanina. Nepoužívejte abrazivní čisticí prostředky nebo rozpouštědla.

6.2. Péče o baterie

Recharge the NiMH batteries when the low battery indicator appears. If the instrument will not be used for an extended period, it is recommended to fully charge the batteries and store the device in a cool, dry place.

6.3. Výměna pojistky

The instrument uses a 0.315 A fuse (part number 757211). If a fuse blows, ensure the instrument is off and disconnected from all circuits before replacing it. Only use fuses of the specified type and rating.

7. Řešení problémů

  • Přístroj se nezapne: Check battery charge level. Ensure batteries are correctly inserted.
  • Nepřesné údaje: Ensure test leads are properly connected and not damaged. Verify the correct measurement function is selected.
  • RCD/FI test fails: Check RCD type and nominal current settings. Ensure the RCD itself is functional.
  • Display shows "OVERLOAD" or "OL": The measured value exceeds the instrument's range for the selected function. Disconnect immediately.

If problems persist, contact Benning customer support or a qualified service technician.

8. Specifikace

FunkceSpecifikace
VýrobceBenning
Číslo modelu044104
Rozměry (D x Š x V)11.5 x 10.3 x 23 cm (4.5 x 4.1 x 9.1 palce)
Hmotnost1.01 kg (2.23 lb)
Napájení6 AA NiMH rechargeable batteries (included)
Rozsah izolačního odporu0.01 MOhm - 1000 MOhm
Zkouška izolace svtages50V, 100V, 250V, 500V, 1000V
Low-Ohm Resistance Range0.01 Ohm - 2000 Ohms (200mA test current)
Loop/Line Impedance Range0.01 Ohm - 10 kOhm
RCD/FI Test TypesAC, A, F (Standard and Delayed 'S')
AC/DC Voltage Dosah1 V - 550 V (True RMS)
Frekvenční rozsah0 Hz - 500 XNUMX Hz
DodržováníDIN VDE 0100-600, IEC 60364-6, DIN VDE 0105-100, EN 50110, IEC
Minimální provozní objemtage50 voltů
Maximální provozní objtage600 voltů

9. Záruka a podpora

Benning provides a 1-year availability for spare parts for the IT 115 Installation Tester. For technical support, service, or warranty claims, please contact your local Benning distributor or visit the official Benning webmísto.